Engine; Protection Systems; Emission Information - Generac Power Systems G007144 Owner's Manual

50 hz air-cooled generator sets
Hide thumbs Also See for G007144:
Table of Contents

Advertisement

General Information

Engine

Model
Type of Engine
Number of Cylinders
Displacement
Cylinder Block
Recommended Spark Plug
Spark Plug Gap
Valve Clearance
Starter
Oil Capacity Including Filter
Oil Consumption
Recommended Oil Filter
Recommended Air Filter
Engine power is subject to and limited by such factors as fuel joules/BTU, ambient temperature and altitude. Engine power decreases about 3.5% for
each 304.8 m (1000 ft) above sea level, and also will decrease about 1% for each 6 °C (10 °F) above 15 °C (60 °F) ambient temperature.
A detailed specification sheet for your particular generator set is available from your local Independent Authorized
Service Dealer (IASD) or at www.generac.com.

Protection Systems

The generator set may need to run for long periods of
time with no operator present to monitor the engine/
generator conditions. The generator set is equipped with
protection systems to automatically shut down the unit to
protect against potentially damaging conditions. Some of
these systems include:
Alarms:
High Temperature
Low Oil Pressure
Overcrank
Overspeed
Overvoltage
Undervoltage
Overload
Warnings:
Charger Warning
Charger Missing AC
Low Battery
Battery Problem
14
8 kVA
G-Force 500 Series
2
530 cc
0.76 mm (0.030 in)
0.05–0.1 mm
(0.002–0.004 in)
Approx. 1.6 L (1.7 qt)
Approx. 5-10 mL per hour (0.17–0.34 oz. per hour) at an average load of 50%
Underspeed
RPM Sensor Loss
Controller Fault
Wiring Error
Stepper Overcurrent
Emergency Stop
Exercise Set Error
USB Warning
Download Failure
Aluminum w/ cast iron sleeve
Replacement Parts
See
12 VDC
Replacement Parts
See
Replacement Parts
See
The control panel contains a display which alerts the
operator when a fault condition occurs. The above list is
not all inclusive. See
about alarms and control panel operation.
NOTE: A warning will indicate a condition on the
generator set which should be addressed, but will not
shut the generator set down. An alarm will shut the
generator set down to protect the system from any
damage. In the event of an alarm, an owner can clear the
alarm and restart the generator set prior to contacting an
IASD. If the intermittent issue occurs again, contact an
IASD.

Emission Information

The engine used in this generator set is not certified to
United States EPA emission standards, or any other
emission standards. Sale or use of this generator set is
not legal in the U.S or any country which has emission
standards applicable to this product.
Owner's Manual for 50 Hz Air-Cooled Generator Sets
10 kVA / 13 kVA
G-Force 1000 Series
2
999 cc
1.02 mm (0.040 in)
0.05–0.1 mm
(0.002–0.004 in)
Approx. 1.8 L (1.9 qt)
Operation