Download Print this page

Generac Power Systems Whisper - Test UL 2200 Specification Sheet

70 kw 60 hz liquid cooled gas engine generator sets

Advertisement

Quick Links

Standby Power Rating
70 kW
STANDARD EQUIPMENT
• All input connections in one single area
• High coolant temperature shutdown
• Low oil pressure shutdown
• Low coolant level automatic shutdown
• Low fuel pressure
• Overspeed automatic shutdown
• Adjustable cranking timer
• Adjustable exercise timer
• Oil drain extension
• Cool flow radiator
• Closed coolant recovery system
FEATURES
• Innovative design and fully prototype tested
• UL 2200 Listed
• Solid state frequency compensated voltage regulator
• Dynamic and static battery charger
• Sound attenuated acoustically designed enclosure
• Whisper-Test™ for low noise level exercise
• Acoustically designed engine cooling system
• High flow low noise factory engineered exhaust system
• State of the art digital control system with H-100 microprocessor
control panel
60 Hz
Liquid Cooled Gas Engine Generator Sets
COMMERCIAL SERIES
Whisper-Test™

Low Speed Exercise

61 dB(A) at 23 feet
Transfer Switch is sold separately
• UV/Ozone resistant hoses
• Watertight state of the art electrical connectors
• Mainline circuit breaker
• Oil drain extension to frame rail
• Radiator drain extension
• Battery charge alternator
• 2 Amp static battery charger
• Battery, battery rack and battery cables
• Fan and belt guards
• Isochronous governor
• Flex fuel line pigtail
• Watertight electrical connectors
• Rodent proof construction
• High efficiency, low distortion Generac designed alternator
• Vibration isolated from mounting base
• Matching Generac transfer switches engineered and tested
to work as a system
• All components easily accessible for maintenance
• Electrostatically applied powder paint
• Built-in kW, kVAR and power factor meters
GENERAC 6.8L ENGINE
Naturally Aspirated
Gaseous Fueled
UL 2200 Listed

Advertisement

loading

Summary of Contents for Generac Power Systems Whisper - Test UL 2200

  • Page 1: Low Speed Exercise

    Standby Power Rating 70 kW STANDARD EQUIPMENT • All input connections in one single area • High coolant temperature shutdown • Low oil pressure shutdown • Low coolant level automatic shutdown • Low fuel pressure • Overspeed automatic shutdown • Adjustable cranking timer •...
  • Page 2: Generator Specifications

    APPLICATION & ENGINEERING DATA GENERATOR SPECIFICATIONS TYPE ...Synchronous ROTOR INSULATION ... Class H STATOR INSULATION ... Class H TOTAL HARMONIC DISTORTION ...<3.5% TELEPHONE INTERFERENCE FACTOR (TIF) ... <50 ALTERNATOR OUTPUT LEADS 3 PHASE ...4 wire BEARINGS...Sealed Ball COUPLING ... Flexible Disc LOAD CAPACITY (STANDBY RATING) ...
  • Page 3 COMMERCIAL 70 kW OPERATING DATA KW RATING ENGINE SIZE GENERATOR OUTPUT VOLTAGE/KW - 60 Hz 120/240V, single phase, 1.0 pf 120/208V, 3-phase, 0.8 pf 120/240V, 3-phase, 0.8 pf 277/480V, 3-phase, 0.8 pf GENERATOR LOCKED ROTOR KVA AVAILABLE @ VOLTAGE DIP OF 35% Single phase or 208V &...
  • Page 4 120/240 3 ø 277/480 3 www.guardiangenerators.com © 2007 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. COMMERCIAL 70 kW LUG SIZE 1-600 mcm to 2 - 250 mcm-2- 1/0 1-600 mcm to 2 - 250 mcm-2- 1/0...