ENGINE PROTECTIVE DEVICES

The Stationary Emergency Generator may be required
to operate for long periods of time without an opera-
tor on hand to monitor such engine conditions as
coolant temperature, oil pressure or rpm. For that
reason, the engine has several devices designed to
protect it against potentially damaging conditions by
automatically shutting down the unit when the oil
pressure is too low, the coolant temperature is too
high, the coolant level is too low, or the engine is run-
ning too fast.
Engine protective switches and sensors are men-
tioned here for the reader's convenience. Also
refer to the applicable control panel manual for
additional automatic engine shutdown informa-
tion.

HIGH COOLANT TEMPERATURE SWITCH

The switch will close if the temperature should
exceed approximately 140° C (284° F), initiating an
engine shutdown. The generator will automatically
restart and the LED will reset once the temperature
has returned to a safe operating level.

LOW COOLANT LEVEL SENSOR

To prevent overheating, the engine has a low coolant
level sensor. If the level of engine coolant drops below
the level of the low coolant level sensor, the engine
automatically shuts down.

LOW OIL PRESSURE SWITCH

This switch has normally closed contacts that are
held open by engine oil pressure during cranking and
operating. Should oil pressure drop below the 8 psi
range, switch contacts close, and the engine shuts
down. The unit should not be restarted until oil is
added, and the AUTO/OFF/MANUAL switch must be
turned to OFF and then back to AUTO.
Stationary Emergency Generator
Engine Protective Devices
NOTE:

OVERCRANK SHUTDOWN

After a prespecified duration of cranking, this func-
tion ends the cranking if the engine has failed to
start. The overcrank LED will turn ON. Turn OFF the
AUTO/OFF/MANUAL switch, then turn switch back to
AUTO to reset the generator control board.
If the fault is not corrected, the overcrank feature
will continue to activate.
Approximate Crank Cycle Times
• 15 seconds ON
• 7 seconds OFF
• 7 seconds ON
• 7 seconds OFF
• Repeat for 45 seconds
Approximately 90 seconds total.

OVERSPEED SHUTDOWN

A speed circuit controls engine cranking, start-up,
operation and shutdown. Engine speed signals are
delivered to the circuit board whenever the unit is
running. Should the engine overspeed above a safe,
preset value, the circuit board initiates an automatic
engine shutdown. Contact the nearest Authorized
Dealer if this failure occurs.

RPM SENSOR LOSS SHUTDOWN

If the speed signal to the control panel is lost, engine
shutdown will occur.
DC FUSES
Fuse F1 (15 amp) is located inside of the control
panel. It protects the panel wiring and components
from damaging overload. Always remove this fuse
before commencing work on the generator. The
unit will not start or crank if the fuse is blown.
Fuse F2 (25 amp) is located in the engine wire har-
ness adjacent to the DC alternator. It is used to pre-
vent circuit failure due to DC alternator falure. If this
fuse is blown, battery charging will not occur while
the engine is running. Replace these fuses with the
same size, type, and rating. (See the exploded views
and parts lists at the end of this manual for replace-
ment part number.)