More information about the programming of the timed thermostat with the Easy Configurator is given in the Programming Manual of Easy devices with Easy Controller (which can be downloaded from the website www.gewiss.com).
GENERAL DESCRIPTION Position of the commands The timed thermostat is equipped with a backlit LCD display and four command push- buttons that can always be accessed. ATTENTION! If the display backlighting is enabled, only the screen will light up when any one of the 4 front button keys is pressed for the first time;...
Page 6
GENERAL DESCRIPTION INFORMATION ON THE DISPLAY Symbol Time of day / Variable value of the hourly profile / Value shown on the humidity page (Hr = relative humidity; HA = specific humidity; tr = dew point temperature) Day of the week Programming mode Settings menu Battery charge level...
GENERAL DESCRIPTION Control modes The timed thermostat can be set with 2 different control modes: • Master: the timed thermostat sets the type, operating mode or setpoint of the devices configured as Slaves (e.g. the Easy flush-mounting thermostats GW1x765H). In the first case (mode), the thermostats use the setpoints set locally.
GENERAL DESCRIPTION MEANING OF Heating Cooling Symbol Setpoint Operating mode Setpoint Operating mode Economy Comfort ECONOMY COMFORT Pre-comfort Pre-comfort COMFORT COMFORT Comfort Economy COMFORT ECONOMY The anti-freeze function is only active in heating mode, when the temperature adjustment system is switched OFF. In this case, the timed thermostat uses the fixed anti-freeze temperature setpoint, only reactivating the heating system if the room temperature falls below T...
GENERAL DESCRIPTION During operation, the activation of the heating or cooling mode is indicated in the following way: Heating symbol indicates that the activation command has been sent to the command actuator of the boiler or area solenoid valve. If the timed thermostat does not receive confirmation of effective implementation from the actuator, symbol will begin to flash.
USER INSTRUCTIONS Normal operation In normal operating conditions, the pages containing information about the timed thermostat are visualised. If the sections relating to the hourly timer and humidity were enabled during programming, the relative pages will also be shown. Choosing the page you want to see To access the screen listing the pages that can be viewed (relating to the timed thermostat, hourly timer and humidity), press the...
Page 11
USER INSTRUCTIONS Choosing the fan coil speed If the displayed page relates to the timed thermostat and any HVAC mode other than OFF is active, press simultaneously to access the selection page (the control algorithm of the heating/cooling function must be set on “fan coil”). Use the button key to select the required fan coil setting ( ), then confirm with the button key or wait for the 30-...
Page 12
USER INSTRUCTIONS Holiday function In the Auto, Economy, Pre-comfort and Comfort modes, the Holiday function allows you to temporarily exclude the set operating mode and activate the Economy mode with an adjustable setpoint, for a period of time between 1 and 99 days. This function can be used, for instance, to set the economic operation of the temperature adjustment system during a holiday or a long period of absence, being sure of having the...
Page 13
USER INSTRUCTIONS Copying the holiday program In Auto mode, you can copy the profile of the holiday day onto any day of the week. This function can be activated up to 6 days ahead of the chosen day. It is especially useful when a holiday day falls during the week.
Page 14
USER INSTRUCTIONS Pages relating to the humidity section View the humidity parameters NB: the pages relating to humidity are only active and visible on the display when the relative channel is included in a function with the channel of a humidity sensor (e.g. GW1x762H), during programming with Easy Controller.
Page 15
USER INSTRUCTIONS General parameters Setting the day Access to the Set menu is indicated by the word SET on the display, and by the flashing of the day of the week. Set the day by means of the button keys (MON, TUE, WED, THU, FRI, SAT, SUN).
Page 16
USER INSTRUCTIONS Back-lighting colour Use the button key to modify the colour of the display back-lighting. To confirm your choice and move on to the next parameter, press the button key within 30 seconds. NB: if red/blue is chosen, the timed thermostat background will be white during the idle phase (heating and cooling valves deactivated) of normal operation, turning red when the heating system is activated or blue when the cooling...
Page 17
USER INSTRUCTIONS Back-lighting intensity Use the button key to choose how to manage the back-lighting intensity (MAN = fixed value; SENS = light sensitive sensor). This parameter is only visible if the back- lighting is active. If the type of management is MAN, use button key to choose the required percentage of light intensity (the gap can be set from 30 to 100%).
Page 18
USER INSTRUCTIONS Setting the alarm threshold temperature Use the button key to set the maximum floor-level temperature above which the timed thermostat suspends heating to prevent any possible damage (the value is expressed as tenths of °C, and can be set from 150 to 1000 in steps of 100). This parameter is only visible if the NTC temperature probe sensor connected to the timed thermostat has been enabled as a temperature probe (TEMP).
Page 19
USER INSTRUCTIONS Operating parameters White balancing Use the button keys to set the weight of the red component (RED) in the backlighting of the display (value can be set between 1 and 63). The regulation only applies to the white colour of the screen. To confirm the selection and continue with the next parameter, press the button key within 30 seconds.
Page 20
USER INSTRUCTIONS If the displayed page relates to the timed thermostat (type of operation: heating) Setpoint setting Used to modify the temperature value associated with the setpoint. Adjust the value of ) with the aid of the ECONOMY button keys. To confirm the set value and move on to the next parameter, press the button key within 30 seconds.
Page 21
USER INSTRUCTIONS If the displayed page relates to the timed thermostat (type of operation: cooling) Setpoint setting Used to modify the temperature value associated with the setpoint. Adjust the value of ) with the aid of the COMFORT button keys. To confirm the set value and move on to the next parameter, press the button key within 30 seconds.
Page 22
USER INSTRUCTIONS If the displayed page relates to the hourly timer Setting Used to modify Value 1 of the hourly profile associated with status, if the control variable is other than 1 bit. Adjust the value using the button keys. To confirm the set value and move on to the next parameter, press the button key within 30 seconds.
Page 23
USER INSTRUCTIONS Setting the cyclical profile sending time Used to set the frequency for sending the current hourly profile value on the BUS. This parameter is only effective when the timed thermostat / hourly timer is in Automatic mode. Use the button keys to modify the sending time (OFF = send only with hourly profile variation;...
Page 24
USER INSTRUCTIONS Temperature adjustment control algorithm Use the button key to modify the control algorithm for heating , cooling , or both (2P = two points ON/OFF; PI = PWM proportional-integral; FAN = fan coil with speed control ON/OFF) depending on the type of operation and the control logic set on the previous screens.
Page 25
USER INSTRUCTIONS Setting the adjustment differential Use the button keys to set the value of the adjustment differential of the two-point control algorithm (the gap can be set from 0.1°C to 2.0°C). To confirm your choice and move on to the next parameter, press the button key within 30 seconds.
Page 26
USER INSTRUCTIONS PWM PROPORTIONAL-INTEGRAL The PWM control algorithm, used to control the temperature adjustment system, allows you to drastically reduce the times subject to thermal inertia and introduced by the two- point control. This type of control involves the modulation of the impulse duty-cycle, represented by the temperature adjustment system activation time, on the basis of the difference between the fixed setpoint and the temperature effectively detected.
Page 27
USER INSTRUCTIONS The device keeps the temperature adjustment system switched on for a cycle time percentage that depends on the output function of the proportional-integral control; the device continually adjusts the system, modulating the system ON-OFF times with a duty- cycle that depends on the value of the output function (calculated at each time gap equal to the cycle time).
Page 28
USER INSTRUCTIONS FAN COIL WITH ON-OFF SPEED CONTROL The operating principle involves activating/deactivating the fan coil speeds on the basis of the difference between the fixed setpoint and the detected temperature, using independent 1-bit communication objects to manage the individual speeds. The figures below refer to the control of the speeds of a fan coil with three operating stages for heating and cooling.
Page 29
USER INSTRUCTIONS Speed V1 is activated when the temperature value is lower than the “setpoint - valve ” value (in heating mode) or higher than the “setpoint + ” value 1heat valve 1cond (in cooling mode), and deactivated when the temperature value reaches the “setpoint - ”...
Page 30
USER INSTRUCTIONS Setting the adjustment differential for speed 1 Use the button key to set the value of the adjustment differential of fan coil speed 1 (the gap can be set from 0°C to 2.0°C). If a value of 0°C is set, then when the solenoid valve is activated fan coil speed 1 will be activated as well.
USER INSTRUCTIONS Hourly profile programming To personalise the hourly profile program of the device, call up the main page of the timed thermostat or the general hourly timer profile (make sure the profiles have been enabled with Easy controller), then press the button key twice.
Page 32
USER INSTRUCTIONS NB: if the hourly timer output object has a dimension of 1 bit, 3 values can be set: - no action = no spots; - action associated with value 0 = 1 spot; - action associated with value 1 = 3 spots. Completing the customisation After repeating the above steps to obtain the required hourly profile, you can: - copy the program onto the next day and confirm the programming by pressing the...
Page 33
USER INSTRUCTIONS Easy channel localisation mode To access the Easy channel localisation mode, start from the timed thermostat normal operation screen and press the button key 3 times (the “Enabling supplementary parameter pages” menu must be set on GFC). In this way you can localise the channels implemented by the device, to insert them in the various functions created with the Easy configurator (Easy Controller).
Page 34
USER INSTRUCTIONS SLA (Slave) Used to set: • from remote, with other Easy devices, the type (heating/cooling) and HVAC operating mode of the timed thermostat. Examples of devices that can be used: GSM Easy remote control, Easy command and visualisation panel, Easy 4-channel interface, etc.;...
Page 35
USER INSTRUCTIONS HS1 (Speed 1 of heating fan coil) Used to send the ON/OFF command to the channel of the Easy actuator that controls speed 1 of the heating fan coil. HS2 (Speed 2 of heating fan coil) Used to send the ON/OFF command to the channel of the Easy actuator that controls speed 2 of the heating fan coil.
USER INSTRUCTIONS Pre-set programs The timed thermostat has 2 pre-set programs, one for heating and the other for cooling. HEATING PROGRAM Monday - Friday Saturday - Sunday COOLING PROGRAM Every day of the week These pre-set programs can be modified and customised according to your own particular needs.
Page 37
USER INSTRUCTIONS Day of the week Monday Time 0.00 16 °C 18 °C Heating temperature setpoint 20 °C 5 °C ANTI FREEZE 24 °C 26 °C 28 °C Cooling temperature setpoint 35 °C HIGH TEMPERATURE PROTECTION Temperature measurement unit °C logic, Common control 2 ON-OFF points...
USER INSTRUCTIONS F.A.Q. What does the temperature value on the display actually represent? If no external temperature probe is enabled during programming, the value shown on the display is the temperature detected by the sensor in the timed thermostat. If, however, an external temperature probe (of the Easy or NTC type) has been enabled, the timed thermostat shows the average of the values detected by the probe and the sensor, using a variable weight between 10% and 100% (which can be defined via Easy configurator).
Page 39
USER INSTRUCTIONS F.A.Q. What happens to the time band set on the timed thermostat if the BUS power supply fails and is reset? If the device is fitted with batteries, the time and date are maintained until the battery charge runs out. Is it possible to understand whether the potential-free contact input is open or closed? The timed thermostat display shows whether the contact is closed...
Page 40
According to article 9 paragraph 2 of the European Directive 2004/108/EC, the responsible for placing the apparatus on the Community market is: GEWISS S.p.A Via A. Volta, 1 - 24069 Cenate Sotto (BG) Italy Tel: +39 035 946 111 Fax: +39 035 945 270 E-mail: qualitymarks@gewiss.com +39 035 946 111 sat@gewiss.com...