Input Phase Failure; Output Phase Failure; Motor Self-Learning Failure; Communication Failure - Fuling Inverter DZB200 Series User Manual

High-performance general-purpose inverter. open-loop vector control inverter
Hide thumbs Also See for DZB200 Series:
Table of Contents

Advertisement

Whether it is normal after the
5 / 1 4 / 2 0 1 8
renewal of the main control board
Seek technical support
14. Input phase failure(E012)
Check if the three-phase input power is normal
Yes
Check if the drive board is no rmal
Yes
Check if The main control board is normal
Seek technical support
15. Output phase failure(E013)
Check if the lead wire from frequency
inverter to the motor is normal
Yes
Check if the thre-e p hase output of
frequency inverter is balanced when
running without motor
No
Check if drive board is normal
Yes
Check if the module is normal
Seek technical support
h t t p : / / s l i d e p d f . c o m / r e a d e r / f u l l / f u l i n g - i n v e r t e r - u s e r - m a n u a l
No
main control board fault
Check and remove the problems in
No
the peripheral lines,To make the
three-phase power entering the
frequency inverter normal
No
Change drive board
No
Change main control board
No
Remove peripheral fault
Check if the motor thre -
e
Yes
phase winding is normal,
If no, remove t he fault.
No
Change drive board
No
Change module
- 7 9 -
Check if Hall device is normal
F u l i n g I n v e r t e r U s e r M a n u a l - s l i d e p d f . c o m
Check if the drive board is normal
17. Motor self-learning failure(E016)
The motor parameters are configured
as per the data on the nam eplate or not
The parameters identification process
is overtime or not
18. Communication Failure(E018)
Master station works or not
RS485 communication connection
is normal or not
Baud rate setup is correct or not
Communication parameters F6.02
and F6.03 are correctly set up or not
Seek technical support
No
Change Hall device
Yes
No
Change drive board
Seek technical support
No
Correctly configure the
motor parameters
Yes
Yes
Check the lead wire from
frequency inverter to motor
No
Check master station
connection
Yes
No
Check communication
connection
Yes
No
Correctly set up
baud rate
Yes
No
Change communication
parameters
Yes
- 8 0 -
4 3 / 5 4