Dcbrake Diagram; Fwd/Rev Dead Time Diagram - Fuling Inverter DZB200 Series User Manual

High-performance general-purpose inverter. open-loop vector control inverter
Hide thumbs Also See for DZB200 Series:
Table of Contents

Advertisement

O u tp u t F r e q u e n c y f
5 / 1 4 / 2 0 1 8
O u tp u t
V o lta g e
D C B r a k e
w h e n
s ta r t in g
Fig. 6-3 DCBra ke Diagram
Function
Name
Code
Dead time between
F0.24
forwarda nd reverse
It is to set the transient time during w hich the output frequency is 0 in the FWD/REV transient process
of inverter.
It is shown as following figure:
Output
Frequency f
Forward
Fig. 6-4 FWD/REV Dead Time Diagram
Function
Name
Code
Terminal command
F0.25
protection when
power on
If operating command channel is set to terminal control, s ystem will detect terminal status
automatically during inverter power on.
h t t p : / / s l i d e p d f . c o m / r e a d e r / f u l l / f u l i n g - i n v e r t e r - u s e r - m a n u a l
T im e t
D C B ra k e
T im e t
w h en
s to p p in g
Default
Setting Range
Value
0.0
3600.0s
0.0s
Time t
Reverse
Dead Time
Default
Setting Range
Value
0
Terminal command invalid
when power on
0
1
1
Terminal command valid when
power on
- 4 1 -
0: Terminal command invalid when power on. Inverter will not run if it detect operating command termi nal
F u l i n g I n v e r t e r U s e r M a n u a l - s l i d e p d f . c o m
is valid. When the operating command terminal is inv alid and enable this terminal again, invert er will run.
1: Terminal command valid when power on. Inverter will startup automatically after initiali zation is
finished if it detect operation command terminal is valid.
 Note: Customer should be careful when you select this function, it may cause severe consequence.
F1 Motor Parameters
Function
Name
Code
F1.00
Inverter model
0: suitable for constant torque load of d esignated nominal parameter.
1: suitable for variable torque l oad (such as fan and pump).
Constant torque(B model) inverter can dri ve larger variable torque(P model) load directly.
'
For example,
DZB300B0220L4
fan, you should
Set F1.00 as 1
Set F1 group motor parameter again
Function
Name
Code
Motor rated power
F1.01
Motor rated frequency
F1.02
Motor rated speed
F1.03
Motor rated voltage
F1.04
Motor rated current
F1.05
 Note: please set these codes according to motor na meplate parameters. The superior performances
 of vector control require precise motor parameters.
DZB series inverter provides parameter self-learning function. Accurate parameter self-learning comes
from correct setting of motor nameplate parameters.
In order to ensure the control perform ances, please do the motor setting based on t he inverter standard
adaptive motor. If the motor rated power has a too big difference to the standard adaptive motor, the inverter
control performances will be deteriorated distinctly.
 Note: resetting of motor rated power (F1.01) can initialize motor parameter F1.02-F1.10.
Default
Setting Range
Value
0 B model
Set by
model
1 P model
'
inverter is set 22KW B model as default, if you want to drive 30KW
Default
Setting Range
Value
Set by
0.4 900.0kW
model
0.01Hz F0.04
50.00Hz
Set by
0 36000rpm
model
Set by
0 4 60 V
model
Set by
0.1 1000.0A
model
- 4 2 -
2 4 / 5 4