6-2-2. M-NET transmission cables (Centralized control transmission cables)
1. Attach M3.5 sleeved ring terminals to the M-NET transmission cables (A, B, Shield).
2. Connect the M-NET transmission cables to the M-NET terminal block.
3. Fix the cables in place with the supplied cable tie.
4. When the power is supplied from the unit other than the AE-200 and AE-50, disconnect the M-NET power jumper from CN21.
Cable tie (supplied)
Note
Provide a single point ground for the shield of the centralized control transmission cable. (Provide the appropriate grounding
according to local standards.)
When leaving the M-NET power jumper connected to CN21 on the AE-200/AE-50/EW-50, the M-NET S (shield) terminal of
TB3 is connected to the ground terminal block on the unit, and the ground is supplied via the protective ground wire.
When disconnecting the M-NET power jumper from CN21 on the AE-200/AE-50/EW-50, provide a ground point at a power
supply unit (PAC-SC51KUA).
Properly fix the cable sheaths in place with the supplied cable ties. The distance between the sheath end and the ring
terminal must be 30 mm (1-3/16 in) or less.
WT07935X04
CN21
30 mm (1-3/16 in) or less
M-NET transmission cable S (Shield)
M-NET transmission cables A and B (Non-polarized)
Sheath
To outdoor unit
Cable tie (supplied)
Cable sheath
19