6-2. Connecting AC power cables and M-NET transmission cables

AE-200/AE-50
6-2-1. AC power cables and protective ground wire
1. Attach M3.5 sleeved ring terminals to the AC power cables, and attach an M4.0 sleeved ring terminal to the protective ground
wire.
2. Connect the AC power cables to the power supply terminal block, and connect the protective ground wire to the ground
terminal.
Note: Thread the protective ground wire through the guides to prevent the wire from moving when it is retightened to the ground terminal.
3. Fix the cables in place with the supplied cable tie.
30 mm
(1-3/16 in)
or less
AC power cable
Cable tie (supplied)
Sheath
Note
Make the protective ground wire 25 mm (1 in) longer than the AC power cables (L/L1, N/L2).
Properly fix the cable sheaths in place with the supplied cable ties. The distance between the sheath end and the ring
terminal must be 30 mm (1-3/16 in) or less.
WT07935X04
M-NET transmission cables
for centralized control
AC power cables
Protective
ground wire
Cable tie (supplied)
Cable sheath
18
Outdoor unit
TB7
Overcurrent breaker
100–240 VAC
Earth leakage breaker
100–240 VAC