S-Bus Sensor Wiring
The labels on the sensors and controller are color coded
for ease of installation. Orange labeled sensors can only be
wired to orange terminals on the controller. Brown labeled
sensors can only be wired to S-bus (brown) terminals. Use
Fig. 52 and Table 6 to locate the wiring terminals for each S-
Bus sensor.
Use Fig. 52 and Table 7 to set the DIP switches for the de-
sired use of the sensor.
S-BUS
TERMINALS
(1 AND 2)
Fig. 52 — S-Bus Sensor DIP Switches
Table 6 — Enthalpy Control Sensor Wiring
Terminations
TERMINAL
NUMBER
LABEL
1
S-BUS
2
S-BUS
NOTE: Terminals are polarity insensitive.
Table 7 — Enthalpy Control Sensor
DIP Switch Settings
DIP SWITCH POSITIONS FOR SWITCHES 1, 2, AND 3
USE
1
DA
OFF
RA
ON
OA
OFF
LEGEND
DA — Discharge Air
OA — Return Air
RA — Outside Air
NOTE: When an S-Bus sensor is connected to an existing net-
work, it will take 60 minutes for the network to recognize and
auto-configure itself to use the new sensor. During the 60-minute
setup period, no alarms for sensor failures (except SAT) will be
issued and no economizing function will be available.
DIP
SWITCH
LABEL
DIP
SWITCHES
(3)
S-BUS
2 PIN SIDE
CONNECTOR
TYPE
DESCRIPTION
S-BUS
Communications
S-BUS
(Enthalpy Control
Sensor Bus)
S-BUS
Communications
S-BUS
(Enthalpy Control
Sensor Bus)
2
3
ON
OFF
OFF
OFF
OFF
OFF
CO
Sensor Wiring
2
When using a CO
wires are internally connected and only one is connected to
"IAQ COM" on the W7220. Use the power from the W7220
to power the CO
sensor OR make sure the ground for the
2
power supplies are common. See Fig. 53 for CO
wiring.
CO
SENSOR
2
24V
ANALOG
OUT
1
POWER SUPPLY. PROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
Fig. 53 — CO

INTERFACE OVERVIEW

This section describes how to use the EconoMi$er
interface for:
• Keypad and menu navigation
• Settings and parameter changes
• Menu structure and selection
User Interface
The user interface consists of a 2-line LCD display and a
4-button keypad on the front of the economizer controller.
Keypad
Use the four navigation buttons (see Fig. 54) to scroll
through the menus and menu items, select menu items, and to
change parameter and configuration settings.
To use the keypad when working with menus:
Press the ▲ (Up arrow) button to move to the previous
menu.
Press the ▼ (Down arrow) button to move to the next
menu.
Press the
(Enter) button to display the first item in
the currently displayed menu.
Press the
(Menu Up/Exit) button to exit a menu's item
and return to the list of menus.
MENU UP
SCROLL
(EXIT)
UP/DOWN
BUTTON
BUTTONS
Fig. 54 — W7220 Controller
35
sensor the black and brown common
2
RED
L1
(HOT)
BLACK
L2
1
YELLOW
+
BROWN
ORANGE
GREEN
Sensor Wiring
2
SELECT
(ENTER)
BUTTON
sensor
2
®
user
2 LINE
LCD