ENTHALPY SETTINGS

When the OA temperature, enthalpy and dew point are be-
low the respective setpoints, the outdoor air can be used for
economizing. Figure 55 shows the new single enthalpy
boundaries in the W7220. There are 5 boundaries (setpoints
ES1 through ES5), which are defined by dry bulb tempera-
ture, enthalpy and dew point.
Refer to Table 18 for ENTH CURVE setpoint values.
The W7220 calculates the enthalpy and dew point using
the OA temperature and humidity input from the OA enthal-
py sensor. When the OA temperature, OA humidity and OA
dew point are all below the selected boundary, the economiz-
er sets the economizing mode to YES, economizing is
available.
ECONOMIXING
AVAILABLE
NOT AVAILABLE
TEMPERATURE
Table 18 — Single Enthalpy and Dual Enthalpy High Limit Curves (EN Units)
ENTHALPY
TEMP
CURVE
DRY BULB (°F)
ES1
80.0
ES2
75.0
ES3
70.0
ES4
65.0
ES5
60.0
HL
86.0
Fig. 55 — Single Enthalpy Curve and Boundaries
TEMP
ENTHALPY
DEWPOINT (°F)
(btu/lb/da)
60.0
28.0
57.0
26.0
54.0
24.0
51.0
22.0
48.0
20.0
66.0
32.4
When all of the OA conditions are above the selected
boundary, the conditions are not good to economize and the
mode is set to NO.
Fig. 55 shows the 5 current boundaries. There is also a
high limit boundary for differential enthalpy. The high limit
boundary is ES1 when there are no stages of mechanical
cooling energized and HL (high limit) when a compressor
stage is energized.
Table 18 provides the values for each boundary limit.
SINGLE ENTHALPY
P2 (T,RH)
ES5
POINT P1
HUMIDITY (%
TEMP(°F)
RH)
80.0
36.8
75.0
39.6
70.0
42.3
65.0
44.8
60.0
46.9
86.0
38.9
45
DUAL ENTHALPY
HIGH LIMIT
P1
(T,RH)
ES4
ES3
ES2
ES1
HL
POINT P2
HUMIDITY (%
(°F)
66.3
63.3
59.7
55.7
51.3
72.4
RH)
80.1
80.0
81.4
84.2
88.5
80.3