Carrier PAD4 K Series Installation Instructions Manual

Carrier PAD4 K Series Installation Instructions Manual

13.4 seer2 single-packaged air conditioner system with r-410a refrigerant

Advertisement

Quick Links

PAD4 Series K WPA4 Series K
13.4 SEER2 Single-Packaged Air Conditioner System with R-410A Refrigerant
Single Phase 2-5 Nominal Tons (Sizes 24-60)
Three Phase 3-5 Nominal Tons (Sizes 36-60)
IMPORTANT: Effective January 1, 2015, all split system and packaged
air conditioners must be installed pursuant to applicable regional
efficiency standards issued by the Department of Energy.
NOTE: Read the entire instruction manual before starting the
installation.
NOTE:
Installer: Make sure the Owner's Manual and Service
Instructions are left with the unit after installation.

Table of Contents

Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Receiving and Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Pre-Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Start-up Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Fig. 1 - Unit PAD4, WPA4

Safety Considerations

Improper installation adjustment, alteration, service, maintenance, or use
can cause explosion, fire, electrical shock, or other conditions which
may cause death, personal injury, or property damage. Consult a
qualified installer, service agency, or your distributor or branch for
information or assistance. The qualified installer or agency must use
factory-authorized kits or accessories when modifying this product Refer
to the individual instructions packaged with the kits or accessories when
installing.
Follow all safety codes. Wear safety glasses, protective clothing, and
work gloves. Use quenching cloth for brazing operations. Have a fire
extinguisher available. Read these instructions thoroughly and follow all
warnings or cautions included in literature and attached to the unit.
Consult local building codes, the current editions of the National
Electrical Code (NEC) NFPA 70.
In Canada refer to the current editions of the Canadian electrical Code
CSA C22.1.
Installation Instructions
A09034
Recognize safety information. This is the safety-alert symbol
you see this symbol on the unit and in instructions or manuals, be alert to
the potential for personal injury. Understand these signal words;
DANGER, WARNING, and CAUTION. These words are used with the
safety-alert symbol. DANGER identifies the most serious hazards which
will result in severe personal injury or death. WARNING signifies
hazards which could result in personal injury or death. CAUTION is
used to identify unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability, or
operation.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing system, always turn off main power to
system and install lockout tag. There may be more than one disconnect
switch. Turn off accessory heater power switch if applicable.
WARNING
!
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to relieve system pressure could result in personal injury and/or
death.
1.
Relieve pressure and recover all refrigerant before servicing
existing equipment, and before final unit disposal. Use all
service ports and open all flow-control devices, including
solenoid valves.
2.
Federal regulations require that you do not vent refrigerant into
the atmosphere. Recover during system repair or final unit
disposal.
!
CUT HAZARD
Failure to follow this caution may result in personal injury.
When removing access panels (see
functions inside your unit, be aware of sharp sheet metal parts and
screws. Although special care is taken to reduce sharp edges to a
minimum, be extremely careful and wear appropriate clothing, safety
glasses and gloves when handling parts or reaching into the unit.
CAUTION
Fig.
22) or performing maintenance
. When

Advertisement

loading

Summary of Contents for Carrier PAD4 K Series

  • Page 1: Table Of Contents

    PAD4 Series K WPA4 Series K 13.4 SEER2 Single-Packaged Air Conditioner System with R-410A Refrigerant Single Phase 2-5 Nominal Tons (Sizes 24-60) Three Phase 3-5 Nominal Tons (Sizes 36-60) Installation Instructions IMPORTANT: Effective January 1, 2015, all split system and packaged Recognize safety information.
  • Page 2: Introduction

    Step 2 – Provide Unit Support WARNING IMPORTANT: The unit must be secured to the curb by installing screws through the bottom of the curb flange and into the unit base rails. PERSONAL INJURY AND PROPERTY DAMAGE When installing large base units onto the common curb, the screws must HAZARD be installed before allowing the full weight of the unit to rest on the curb.
  • Page 3 PAD4 Series K WPA4 Series K: Installation Instructions A2301294 Fig. 2 – PAD4 24-30 Unit Dimensions Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 4 PAD4 Series K WPA4 Series K: Installation Instructions A230131 Fig. 3 – WPA4 24-30 Dimensions Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 5 PAD4 Series K WPA4 Series K: Installation Instructions A230130 Fig. 4 – PAD4 36-48 Unit Dimensions Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 6 PAD4 Series K WPA4 Series K: Installation Instructions A230132 Fig. 5 – WPA4 36-60 Unit Dimensions Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 7 PAD4 Series K WPA4 Series K: Installation Instructions SMALL/COMMON CURB SMALL SUPPLY BASE UNIT LARGE BASE RETURN UNIT UNIT PLACEMENT ON COMMON CURB SMALL OR LARGE BASE UNIT LARGE CURB A180216 UNIT CATALOG (small/common (large base) SIZE NUMBER base) IN. (mm) IN.
  • Page 8 PAD4 Series K WPA4 Series K: Installation Instructions CAUTION - NOTICE TO RIGGERS PRUDENCE - AVIS AUX MANIPULATEUR ACCESS PANELS MUST BE IN PLACE WHEN RIGGING. PANNEAUX D'ACCES DOIT ÊTRE EN PLACE POUR MANIPULATION. Use top skid as spreader bar. / Utiliser la palette du haut comme barre de répartition DUCTS MINIMUM HEIGHT: 36"...
  • Page 9 PAD4 Series K WPA4 Series K: Installation Instructions 1. Application of the lifter to the load, and adjustment of the lifts to After the unit is placed on the roof curb or mounting pad, remove the top adapt to various sizes or kinds of loads. skid.
  • Page 10 PAD4 Series K WPA4 Series K: Installation Instructions IMPORTANT: Use flexible connectors between ductwork and unit to Adequately insulate and weatherproof all ductwork located prevent transmission of vibration. Use suitable gaskets to ensure outdoors. Insulate ducts passing through unconditioned space, and weather-tight and airtight seal.
  • Page 11 PAD4 Series K WPA4 Series K: Installation Instructions CAUTION HIGH VOLTAGE POWER LEADS UNIT COMPONENT DAMAGE HAZARD POWER (SEE UNIT WIRING SUPPLY LABEL) Failure to follow this caution may result in damage to the unit being 3-PHASE SHOWN installed. 1-PHASE USES Make all electrical connections in accordance with NFPA 70 TWO POWER EQUIP GR...
  • Page 12 PAD4 Series K WPA4 Series K: Installation Instructions Provide a drip loop before running wires through panel. Secure and strain relief all wires so that they do not interfere with operation of unit. If an accessory electric heater is installed, low voltage leads from heater must be connected to factory supplied control leads from Indoor Fan Board P4 connector.
  • Page 13 PAD4 Series K WPA4 Series K: Installation Instructions Table 1 – Physical Data-Unit UNIT SIZE NOMINAL CAPACITY (ton) 2-1/2 3-1/2 SHIPPING WEIGHT lb. SHIPPING WEIGHT (kg) Scroll COMPRESSORS Quantity REFRIGERANT (R-410A) Quantity lb 5.75 10.75 Quantity (kg) REFRIGERANT METERING DEVICE Orifice ORIFICE ID in./mm .059 / 1.5...
  • Page 14: Pre-Start-Up

    PAD4 Series K WPA4 Series K: Installation Instructions Pre-Start-up Proceed as follows to locate and repair a refrigerant leak and to charge the unit: WARNING 1. Locate leak and make sure that refrigerant system pressure has been relieved and reclaimed from both high- and low-pressure ports. 2.
  • Page 15 PAD4 Series K WPA4 Series K: Installation Instructions attached to the inside of the compressor access panel. (See Fig. 20 This unit is factory-set up for use with a single cooling fan speed. In Subcool chart for units with TXV and superheat chart for units with addition, this unit has the field-selectable capability to run two different fixed orifice.) The chart includes the required liquid line temperature at cooling fan speeds: The rated cooling fan speed (350~400 CFM/Ton)
  • Page 16 PAD4 Series K WPA4 Series K: Installation Instructions – interface board (IFB). Verify that static pressure is in the acceptable Table 3 – Color Coding for Indoor Fan Motor Leads range for the speed tap to be used for dehumidification cooling. Black = High Speed 7.
  • Page 17 Table 4 – Dry Coil Air Delivery* - Horizontal and Downflow Discharge Sizes 24-60 ESP (in. W.C.) Unit Size Motor Speed Blue 0.07 0.08 0.08 0.09 Med-Low Pink 0.12 0.13 0.13 0.13 0.14 0.14 0.15 1080 1025 Medium** 0.21 0.22 0.23 0.23 0.24...
  • Page 18 Table 4 – Dry Coil Air Delivery* - Horizontal and Downflow Discharge Sizes 24-60 (Continued) ESP (in. W.C.) Unit Size Motor Speed Blue 0.13 0.13 0.14 0.15 0.16 0.16 0.17 0.18 0.18 0.19 1201 1153 1107 1060 1012 Med-Low Pink 0.21 0.22 0.22...
  • Page 19 Table 5 – Wet Coil Pressure Drop (IN. W.C.) Unit Standard CFM (SCFM) Size 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 0.03 0.04 0.04 0.05 0.06 0.05 0.06 0.07 0.08 0.11 0.06 0.06 0.09 0.10 0.11 0.14...
  • Page 20 PAD4 Series K WPA4 Series K: Installation Instructions A221589 Fig. 14 – Connection Wiring Diagram 208/230-1-60 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 21 PAD4 Series K WPA4 Series K: Installation Instructions A221590 Fig. 15 – Ladder Wiring Diagram 208/230-1-60 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 22 PAD4 Series K WPA4 Series K: Installation Instructions A221587 Fig. 16 – Connection Wiring Diagram 208/230-3-60 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 23 PAD4 Series K WPA4 Series K: Installation Instructions A221588 Fig. 17 – Ladder Wiring Diagram 208/230-3-60 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 24 PAD4 Series K WPA4 Series K: Installation Instructions A221585 Fig. 18 – Connection Wiring Diagram 460-3-60 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 25 PAD4 Series K WPA4 Series K: Installation Instructions A221586 Fig. 19 – Ladder Wiring Diagram 460-3-60 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 26 PAD4 Series K WPA4 Series K: Installation Instructions Superheat charging table is derived from optimum performance point. (95_F [35_C] outdoor ambient and (80_F [27_C] dry bulb; 67_F [19_C] wet bulb indoor condition.) Where a dash(--) appears do not attempt to check charge or charge unit under these conditions using the superheat method. (Weigh in method should be used.) A150625 A230061 Fig.
  • Page 27: Maintenance

    PAD4 Series K WPA4 Series K: Installation Instructions Maintenance cooling season and twice during the heating season, or whenever the filter becomes clogged with dust and lint. To ensure continuing high performance, and to minimize the possibility Indoor Blower and Motor of premature equipment failure, periodic maintenance must be NOTE: All motors are pre-lubricated.
  • Page 28 PAD4 Series K WPA4 Series K: Installation Instructions FAN GRILLE MOTOR MOTOR SHAFT A08505 MAX DISTANCE BETWEEN TOP OF FAN GRILLE AND BOTTOM OF FAN BLADE “A” Size Fig. 21 – Fan Blade Position matter from the pan. Flush the pan and drain trough with clear water. Do not splash water on the insulation, motor, wiring, or air filter(s).
  • Page 29 PAD4 Series K WPA4 Series K: Installation Instructions suspected malfunction has occurred, check each electrical component kPa). High pressure may be caused by a dirty condenser coil, failed fan with the proper electrical instrumentation. Refer to the unit wiring label motor, or condenser air recirculation.
  • Page 30: Troubleshooting

    PAD4 Series K WPA4 Series K: Installation Instructions Liquid Line Filter Drier immediately cleaned up, may cause embrittlement (leading to cracking) to occur in one year or more. When performing any service that may risk The filter drier is specifically designed to operate with R-410A. Use only exposure of compressor oil to the roof, take appropriate precautions to factory-authorized components.
  • Page 31 PAD4 Series K WPA4 Series K: Installation Instructions Table 10 – Troubleshooting Chart SYMPTOM CAUSE REMEDY Power failure Call power company Fuse blown or circuit breaker tripped Replace fuse or reset circuit breaker Defective contactor, transformer, control relay, or Replace component high-pressure, loss-of-charge or low-pressure switch Compressor and outdoor fan will not start Insufficient line voltage...
  • Page 32 REFRIGERANT DISCHARGE ____________ PSIG, LIQUID TEMP† _______________________ ( ) VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS * Measured at suction inlet to compressor {Measured at liquid line leaving condenser. © 2023 Carrier. All rights reserved. Edition Date: 02/23 Catalog No: PAD4-WPA4-02SI A Carrier Company Replaces: PAD4-WPA4-01SI Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.