Economi$Er ® X (Factory Option) - Carrier WeatherMaster Series Installation Instructions Manual

Single package rooftop
Hide thumbs Also See for WeatherMaster Series:
Table of Contents

Advertisement

®
Economi$er
X (Factory Option)
The EconoMi$er X system is an expandable economizer
control system, which includes a W7220 economizer module
(controller) with an LCD and keypad (See Fig. 50). The
W7220 can be configured with optional sensors.
Fig. 50 — W7220 Economizer Module
The W7220 economizer module can be used as a stand-
alone economizer module wired directly to a commercial set-
back space thermostat and sensors to provide outside air dry-
bulb economizer control.
The W7220 economizer module can be connected to op-
tional sensors for single or differential enthalpy control. The
W7220 economizer module provides power and communica-
tions for the sensors.
The W7220 economizer module automatically detects sen-
sors by polling to determine which sensors are present. If a
sensor loses communications after it has been detected, the
W7220 economizer controller indicates a device fail error on
its LCD.
System Components
The EconoMi$er X system includes an economizer mod-
ule, 20k mixed air sensor, damper actuator, and either a 20k
outdoor air temperature sensor or S-Bus enthalpy sensors.
Economizer Module
The module is the core of the EconoMi$er X system. The
module is mounted in the unit's control box, and includes the
user interface for the system. The W7220 economizer module
provides the basic inputs and outputs to provide simple econ-
omizer control. When used with the optional sensors, the
economizer module provides more advanced economizer
functionality.
S-Bus Enthalpy Control Sensors
The sensor is a combination temperature and humidity
sensor which is powered by and communicates on the S-Bus.
Up to three sensors may be configured with the W7220 econ-
omizer module.
CO
Sensor (optional)
2
The sensor can be added for Demand Controlled Ventila-
tion (DCV).
Specifications
W7220 Economizer Module
The module is designed for use with 2 to 10 Vdc or bus
communicating actuator. The module includes terminals for
CO
sensor, Mixed Air sensor, and an Outdoor Dry Bulb sen-
2
sor. Enthalpy and other options are available with bus
sensors.
User Interface
Provides status for normal operation, setup parameters,
checkout tests, and alarm and error conditions with a 2-line
16 character LCD display and four button keypad.
Electrical
• Rated Voltage — 20 to 30 Vac RMS, 50/60 Hz
• Transformer — 100 va maximum system input
• Nominal Power Consumption (at 24 Vac, 60 Hz) — 11.5
VA without sensors or actuators
• Relay Digital Output Rating at 30 Vac (maximum power
from Class 2 input only) — 1.5A run:
3.5A inrush at 0.45PF (200,000 cycles) or
7.5A inrush at 0.45PF (100,000 cycles)
• External Sensors Power Output — 21 Vdc ± 5% at 48mA
IMPORTANT: All inputs and outputs must be Class 2
wiring.
Inputs
Sensors
NOTE: A Mixed Air (MA) analog sensor is required on all
W7220 units; either an Outdoor Air (OA) sensor for dry bulb
change over or an OA bus sensor for outdoor enthalpy change
over is required in addition to the MA sensor. An additional Re-
turn Air (RA) bus sensor can be added to the system for differen-
tial enthalpy or dry bulb changeover. For differential dry bulb
changeover a 20k ohm sensor is required in the OA and a bus
sensor in the RA. DIP switch on RA bus sensor must be set in
the RA position.
Dry Bulb Temperature (optional) and Mixed Air (required),
20k NTC
2-wire (18 to 22 AWG);
Temperature range –40 to 150°F (–40 to 65°C)
Temperature accuracy –0°F/+2°F
Temperature and Humidity, C7400S1000 (optional)
S-Bus; 2-wire (18 to 22 AWG)
Temperature: range –40 to 150°F (–40 to 65°C)
Temperature accuracy –0°F/+2°F
Humidity: range 0 to 100% RH with 5% accuracy.
NOTE: Up to three (3) S-Bus sensors may be connected to the
W7220 economizer module. For outdoor air (OA), return air
(RA) and discharge (supply) air (DA).
4 Binary Inputs — 1-wire 24 Vac + common GND
24 Vac power supply — 20 to 30 Vac 50/60Hz; 100 VA Class 2
transformer.
Outputs
Actuator Signal
2-10 Vdc; minimum actuator impedance is 2k ohm; bus
two-wire output for bus communicating actuators.
Exhaust fan, Y1, Y2 and AUX1 O
All Relay Outputs (at 30 Vac):
Running: 1.5A maximum
Inrush: 7.5A maximum
Environmental
Operating Temperature
–40 to 150°F (–40 to 65°C).
Exception of display operation down to –4°F (–20°C) with
full recovery at –4°F (–20°C) from exposure to –40°F
(–40°C)
Storage Temperature
–40 to 150°F (–40 to 65°C)
33

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents