Carrier WeatherMaster Series Installation Instructions Manual page 39

Single package rooftop
Hide thumbs Also See for WeatherMaster Series:
Table of Contents

Advertisement

MENU
PARAMETER
INSTALL
UNITS DEG
EQUIPMENT
AUX2 IN
FAN SPEED
SYSTEM SETUP
FAN CFM
AUX1 OUT
OCC
FACTORY DEFAULT
MA LO SET
FREEZE POS
CO2 ZERO
CO2 SPAN
STG3 DLY
ADVANCED
SETUP
SD DMPR POS
DA LO ALM
DA HI ALM
DCVCAL ENA
Table 8 — Menu Structure* (cont)
PARAMETER
PARAMETER
DEFAULT
RANGE AND
VALUE
INCREMENT
01/01/10
N/A
°F
°F or °C
CONV
Conventional or HP
N/A
Shutdown (SD)
Heat (W1)
HP (O)
HP (B)
1 speed
1 speed/2 speed
5000cfm
100 to 15000 cfm;
increment by 100
NONE
NONE
ERV
EXH2
SYS
INPUT
INPUT or ALWAYS
NO
NO or YES
45°F
35 to 55°F
(7°C)
(2 to 18°C);
incremented by 1°
CLO
CLO or MIN
0ppm
0 to 500 ppm;
Increment by 10
2000ppm
1000 to 3000 ppm;
Increment by 10
2.0h
0 min, 5 min, 15 min,
then 15 min intervals.
Up to 4 hrs or OFF
CLO
CLO or OPN
45°F (7°C)
35 to 65°F (2 to
18°C); incremented
by 5 deg.
80°F (27°C)
70 to 180°F (21 to
82°C); incremented
by 5 deg.
MAN
MAN (manual)
AUTO
39
Display order = MM/DD/YY
Setting order = DD, MM, then YY.
Sets economizer controller in degrees Fahrenheit or Celsius
CONV = conventional;
HP O/B = Enable Heat Pump mode. Use AUX2 I for Heat Pump input
from thermostat or controller.
See Note 4.
In CONV mode:
SD = Enables configuration of shutdown (default);
W = Informs controller that system is in heating mode.
NOTE: If using 2-speed fan mode, you must program CONV mode for W.
Shutdown is not available in 2-speed fan mode. See Note 4.
In HP O/B mode:
HP(O) = energize heat pump on Cool (default);
HP(B) = energize heat pump on heat.
Sets the economizer controller for operation of 1 speed or 2 speed supply
fan. The controller does not control the fan but positions the OA and RA
dampers to the heating or cooling mode. See page 35 for modes and
position.
NOTE: 2-speed fan option also needs Heat (W1) programmed in AUX 2
In. See Note 4.
UNIT DESIGN AIRFLOW (CFM)
Enter only if using DCVAL ENA = AUTO
The value is found on the nameplate label for the specific unit.
Select OUTPUT for AUX1 O relay
• NONE = not configured (output is not used)
• ERV = Energy Recovery Ventilator
• EXH2 = second damper position 24 Vac out for second exhaust fan
• SYS = use output as an alarm signal
OCCUPIED MODE BY EXTERNAL SIGNAL
When using a setback thermostat with occupancy out (24 vac), the 24 vac
is input "INPUT" to the OCC terminal. If no occupancy output from the
thermostat then change program to "ALWAYS" OR add a jumper from ter-
minal R to OCC terminal. See Note 1.
Resets all set points to factory defaults when set to YES. LCD will briefly
flash YES and change to NO but all parameters will change to the factory
default values.
NOTE: RECHECK AUX2 IN and FANTYPE for required 2-speed values.
SUPPLY AIR TEMPERATURE LOW LIMIT
Temperature to achieve Freeze Protection (close damper and alarm if
temperature falls below setup value).
FREEZE PROTECTION DAMPER POSITION
Damper position when freeze protection is active
CLO = closed
MIN = MIN POS or VENTMAX
CO
ppm level to match CO
2
2
CO
ppm span to match CO
2
2
be 500 CO
zero and 1000 CO
2
COOLING STAGE 3 DELAY
Delay after stage 2 cool has been active. Turns on second stage of cool-
ing when economizer is first stage call and mechanical cooling is second
stage call. Allows three stages of cooling, 1 economizer and 2 mechani-
cal.
OFF = no Stage 3 cooling
Indicates shutdown signal from space thermostat or unitary controller.
When controller receives 24 Vac input on the SD terminal in conventional
mode, the OA damper will open if programmed for OPN and OA damper
will close if programmed for CLO. All other controls, e.g., Y1-O, Y2-O,
EXH1, etc. will shut off.
NOTE: Function NOT AVAILABLE with 2-speed mode
Used for alarm for when the DA air temperature is too low. Set lower
range of alarm, below this temperature the alarm will show on the display.
Used for alarm for when the DA air temperature is too high. Set high
range of alarm, above this temperature the alarm will show on the display.
Turns on the DCV automatic control of the dampers. Resets ventilation
based on the RA, OA, and MA sensor conditions. Requires all sensors
(RA, OA, MA, and CO
).
2
NOTE: This operation is not available with a 2-speed fan unit.
NOTES
††
sensor start level.
sensor: e.g. 500-1500 sensor output would
span.
2