Wiring
3.1 Pin assignment of the I/O module DI 8x24...125VDC HA
General pin assignment
Table 3-1
Terminal assignment of the DI 8×24...125VDC HA
Terminal
Assignment
1
DI
0
3
DI
2
5
DI
4
7
DI
6
9
2M
11
2M
13
2M
15
2M
1P1
L+
2P1
L+
Notice
Note differences in potential
The load supply voltage and the signal voltage of the I/O module are elec‐
trically isolated.
● The connection of the load supply voltage and the signal voltage is
only permissible when no compensating currents are flowing as a
result of a difference in potential.
● The connection of additional, external devices to terminals with the
assignment 2M is not permissible. The additional load may result in
the destruction of the I/O module as well as further faults.
10
Terminal
Assignment
2
DI
1
4
DI
3
6
DI
5
8
DI
7
10
2M
12
2M
14
2M
16
2M
1P2
M
2P2
M
Explanations
DI
: Input signal, channel n
n
2M: Signal voltage
1P1: Supply voltage L+ of the voltage bus 1P
2P1: Supply voltage L+ of the voltage bus 2P
1P2: Ground reference of the voltage bus 1P
2P2: Ground reference of the voltage bus 2P
1 DI.0+
DI
DI.1+
3 DI.2+
DI.3+
5 DI.4+
DI.5+
7 DI.6+
DI.7+
9
2M
11
13
15
1P1 L+ 24VDC
2P1 L+ 24VDC
MAX. 10 A
Connection of a digital 2-wire sensor
Digital input module DI 8x24...125VDC HA (6DL1131-6DF00-0PK0)
2
4
6
8
10
12
14
16
M 1P2
M 2P2
2-wire
Manual, 11/2017, A5E39288633-AB