Changing Components - Vent-Axia HR205 User, Installation & Servicing Instructions

House ventilation system with heat recovery and cooker hood
Table of Contents

Advertisement

Bulkhead
Controller
Controller
securing
screws (4 off)
Rear View of the Controller
160
140
120
100
80
L
N
Warning
HR205
Overheat
Thermostat
Head
Overheat
Overheat
Thermostat
Thermostat
Sleeve
Fig. 25
26
Take note of the fan speed setting,
120v shown. When the new controller
is fitted, fit the white lead to the
position of the old controller for the
correct fan speed.
UP
FRONT
Remove RH fan cover
panel & bottom cover panel.
Cable
Tie
Bulkhead
Grommet
Clip

10.0 Changing Components

IMPORTANT: ISOLATE FROM THE
Mounting
ELECTRICAL SUPPLY BEFORE STARTING
bracket to
ANY WORK ON THE APPLIANCE.
bulkhead
securing
The fans continue to rotate for one minute after
screws (2 off)
isolating from the electrical supply
Controller
10.1
Mounting
1. HR205 Only - Fully extend the telescopic
Bracket
cooker hood and remove the two metal filters.
2. Remove the outer door by releasing the two
screws and lifting the door up and forwards.
3. Remove the bottom electrical cover by
releasing the 3 screws, pulling the panel
forwards and disconnecting the earth lead to the
panel. Make a note of the voltage setting for the
fans and of the wiring arrangement for the
controller.
Controller
4. Release all the wires connected to the
controller.
5. Remove R.H. fan cover panel and remove the
R.H. fan (see Section 10.3). Unscrew the two
screws securing the controller mounting bracket
to the bulkhead and remove the bracket and
controller unit. Separate the bracket from
controller by removing the four screws.
6. Re-assemble with the new controller in
reverse order. Check the electrical installation
for; Earth continuity, short circuits,
resistance to earth and correct polarity.
10.2
1. Lift off the front door panel by releasing the
two hand screws and lifting upwards.
2. Remove the bottom electrical cover by
releasing the 3 screws, pulling the panel
forwards and disconnecting the earth lead to the
panel. Identify the connections for the overheat
thermostat. Make a note of the routing for the
overheat thermostat cable.
3. Release the overheat thermostat connections.
4. Release the sensor head by springing open
the clip and pulling out the sensor head.
5. Remove the overheat thermostat taking care
not to dislodge the bulkhead grommet.
6. Carefully locate the new sensor and position
the lead as shown in Fig. 26. Re-assemble with
the new overheat thermostat in reverse order.
Check the electrical installation for; Earth
continuity, short circuits, resistance to earth
and correct polarity.