P2 Error; Over Temperature Protector Located On Compressor; Cn516 Connector Plug Located On Main Outdoor Pcb - Electrolux Kelvinator KSV26HRB Diagnostic Manual

Table of Contents

Advertisement

P2 error

:
# If the P2 error is appearing while the unit has been in operation, check the following points:
• Refrigerant charge.
• Restrictions within the capillary tube.
• Amperage draw in accordance to the "rated current" specification illustrated on the rating plate.
# Check the over temperature protector located next to the three compressor terminals.
Note: This overload is "normally closed".
# Check the CN516 connector plug located on the outdoor main PCB for correct termination &
continuity to the over temperature protector.

Over Temperature Protector located on compressor.

CN516 connector plug located on main outdoor PCB.

Page 21 KSSSI92