P1 Error - Electrolux Kelvinator KSV26HRB Diagnostic Manual

Table of Contents

Advertisement

# Measure the resistance value of the windings on the compressor.
The resistance value should be the same value across any terminal combination.
Note: The resistance values will change in accordance to Capacity & Ambient temperatures.
Common, Start & Run terminal points.

P1 error:

# Check the supply voltage to the indoor unit.
Is it within 160 to 270 Volts?
Note: If the voltage is below 200 Volts, this can reduce the condenser fan speed, thus reducing the unit's
efficiency.
Note: If the supply voltage is okay & P1 fault still exists, replace the outdoor main PCB assembly.
Page 23 KSSSI92