If E1 fault has not cleared:
Check the continuity of the "Bridge Rectifier" on the inverter module as illustrated below.
Turn off the power & let the inverter electrolytic capacitors completely discharge.
Identify the diodes individual 'Plus' and 'Minus' connections so as to test each diode's forward and
reverse resistance values. The diagrams listed below illustrate the method of achieving this.
Set the multimeter to a DC Mega Ohms setting.
Place the Positive probe on the
Place the Positive probe on the
Note: Insure the multimeter probes are placed in their correct orientation as specified above.
Note: If any of the above tests indicate a "Short Circuit" replace outdoor inverter module.
All of the above tests should read several Mega Ohms.
Page 8 KSSSI92
~
pin of the rectifier & the Negative probe on the
-
pin of the rectifier & the Negative probe on the
Relevant test points on the outdoor inverter module.
+
pin of the rectifier.
~
pin of the rectifier.