CONTROLLER
Alarm Data
Table 34: Alarm Data, continued.
Alarm ID
Alarm Screen Line 1
320
Low Suction Pressure
321
High Current
322
High Pressure Ratio
323
Low Pressure Ratio
324
Low Delta P
325
High Discharge Press
326 -327
WSHP Freeze
328 - 329
Low Entering Water
330 - 331
High Entering Water
332
Compressor Staging
333
HP Defrost 3 Strike
334
EVD Error
144
Alarm Screen Line 2
Reset Type
Inverter Compressor
Auto until Lockout 3x in 1 hr Disable Inverter Circuit
Inverter Compressor
Auto until Lockout 3x in 1 hr Disable Inverter Circuit
Inverter Compressor
Auto until Lockout 3x in 1 hr Disable Inverter Circuit
Inverter Compressor
Auto until Lockout 3x in 1 hr Disable Inverter Circuit
Inverter Compressor
Auto until Lockout 3x in 1 hr Disable Inverter Circuit
Inverter Compressor
Auto until Lockout 3x in 1 hr Disable Inverter Circuit
Protection Circuit (x)
Auto
Temp - Circuit (x)
Auto
Temp - Circuit (x)
Auto
Order Skipped
Auto
HP Heating Not Avail
Manual
Unexpected Position
Auto
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Lockout
Action Type
Disable Compressors
Informational
Informational
Informational
Disable HP Heating
Notes
Only with Inverter Scroll
Only with Inverter Scroll
Only with Inverter Scroll
Only with Inverter Scroll
Only with Inverter Scroll
Only with Inverter Scroll
2 hours + Temp Rise for
Reset

Advertisement