CONTROLLER
Set-Points Data Tables
Table 16: Dehumidification Control Set-Points Data Table.
Control Variable
Dehumidification Mode
Inside RH >
Inside Dewpoint >
Outside Dewpoint >
Unoccupied Dehumidification Mode
Inside RH >
Unoccupied Inside
Dewpoint >
Dehumidification Hysteresis
Humidity
Dewpoint
Cold Coil Set-point
Priority Selection
Dehum. →Temp.
Disabled (□)
Heat → Dehum.
Overcool Coil Offset
Dehumidification Force Comp. On
Clg Ramp 1
Table 17: Refrigeration Compressor Control Set-Points Data Table.
Control Variable
Add Deadband
Sub Deadband
Cooling Delays
Interstage
Subtract
Heating Delays
Interstage
Subtract
Re-Add Delay
Min. On
Min. Off
Cold Coil Low Limit Set-
point
Coil Staging Safety Set-
point
Set-point availability varies based on unit configuration.
130
Default
Min.
60%
0%
60.0°F
0.0°F
60.0°F
0.0°F
5%
0%
70.0°F
0.0°F
4%
0%
2.0 Δ°F
0.0 Δ°F
55.0°F
46.0°F
Disabled (□)
Enabled (□)
Disabled (□)
0.0 Δ°F
0.0 Δ°F
Enabled (X)
Disabled (□)
Default
0.5 Δ°F
0.5 Δ°F
60 sec.
60 sec.
60 sec.
60 sec.
300 sec.
60 sec.
270 sec.
42.0°F
46.0°F
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Max.
100%
90.0°F
100.0°F
100%
90.0°F
10%
10.0 Δ°F
80.0°F
Enabled (X)
Enabled (X)
10.0 Δ°F
Enabled (X)
Min.
0.0 Δ°F
20.0 Δ°F
0.0 Δ°F
20.0 Δ°F
10 sec.
600 sec.
10 sec.
600 sec.
10 sec.
600 sec.
10 sec.
600 sec.
10 sec.
600 sec.
1 sec.
600 sec.
1 sec.
600 sec.
35.0°F
35.0°F
Notes
Disabled = Dehumidification Priority;
Enabled = Temperature Priority
Disabled = Heating Priority;
Enabled = Dehumidification Priority
Max.
Notes
55.0°F
55.0°F