Ac Smart Setup - LG AR-DR12-05A Installation And Operation Manual

Rooftop dedicated outdoor air system doas vx, base rooftop doas 800 to 5750 cfm, energy recovery wheel rooftop doas 900 to 9550 cfm
Hide thumbs Also See for AR-DR12-05A:
Table of Contents

Advertisement

CONTROLLER

AC Smart Setup

AC Smart Setup
Only AC Smart 5 or later must be used with CAREL controller. AC Smart 4 is not compatible with CAREL
controller.
1. Confirm control wiring between rooftop unit CAREL controller and AC Smart 5 Channel 1 (Wiring is 18
AWG, 2-conductor, twisted, stranded, shielded, and must comply with all applicable local and national
codes.).
Figure 62: DOAS Controller to AC Smart 5 Connections.
2. On the CAREL controller, under "Network Settings" set the Device I.D. as:
• For AR-DE DOAS models: CAREL Device I.D. = 17 (Decimal) and AC Smart Address = 11 (Hex)
• For AR-DR DOAS models: CAREL Device I.D. = 18 (Decimal) and AC Smart Address = 12 (Hex)
Figure 64: Device I.D. Screen.