LG AR-DR12-05A Installation And Operation Manual page 108

Rooftop dedicated outdoor air system doas vx, base rooftop doas 800 to 5750 cfm, energy recovery wheel rooftop doas 900 to 9550 cfm
Hide thumbs Also See for AR-DR12-05A:
Table of Contents

Advertisement

CONTROLLER
Overview
Table 11: c.pCOe Expansion Board 2 Analog Inputs / Outputs and Digital Outputs.
Analog Inputs
Drawing Reference
Terminal
1
J2
1
J2
1
J2
1
J2
1
J2
1
J2
1
J2
1
J2
1
J2
1
J2
Analog Outputs
Drawing Reference
Terminal
1
J2
Digital Outputs
Drawing Reference
Terminal
2
J10
2
J10
2
J11
2
J11
2
J11
2
J12
2
J12
108
Label
Unit Connection
U1
Analog output
U2
Space CO2 level
U3
Outside air flow measuring station
U4
Supply fan air flow measuring station
U5
Exhaust fan air flow measuring station
U6
OA/RA damper control, BMS input b
U7
Supply fan control, BMS input c
U8
Exhaust fan control, BMS input c
U9
Unassigned
U10
Used as digital input.
Label
Unit Connection
U1
Electric heat capacity output d
Label
Unit Connection
NO1
Unassigned
NO2
Unassigned
NO3
Unassigned
NO4
Unassigned
NO5
Unassigned
NO6
Unassigned
NC6
Unassigned
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Sensor Type
Range
0–10 Vdc
0–2000 ppm
0–10 Vdc
0–1"wc or 0–0.5"wc
0–10 Vdc
0–30" wc
0–10 Vdc
0–30" wc
0–10 Vdc
0–100%
0–10 Vdc
0–100%
0–10 Vdc
0–100%
Sensor Type
Range
0–10 Vdc
0–100%
Position Indicates