Expansion Valve Driver (EVD) Terminal
Connections
Systems use CAREL EVD evolution expansion valve drivers to control electronic expansion
valves, if equipped.
• See the figure and table for terminal connection points.
• See the wiring schematics shipped with the unit for the factory-configured connection
points.
Table 12: Expansion Valve Driver Terminal Connections.
Analog Inputs
Label
Unit Connection
Suction refrigerant pressure
S1
transducer
Suction refrigerant
S2
temperature
S3
Unassigned
Discharge refrigerant
S4
temperature
Digital Inputs
DI-1
Unassigned
DI-2
Unassigned
Electronic Expansion Valve
1
CAREL ExV (green)
3
CAREL ExV (brown)
2
CAREL ExV (yellow)
4
CAREL ExV (white)
Sensor Type
0.5–4.5 V c
CAREL NTC 10K Type 4
CAREL NTC 10K Type 4 HT
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
CONTROLLER
Figure 56: Expansion Valve Driver Terminal
Connections.
Power Supply
EVD evolution
Range
0–250.0 psig
Analog – Digital Inputs
Overview
4
2
3
1
E
V connection A
Relay A
x
Network
GND Tx/Rx
109