Table 23: Occupancy Set-Points Data Table.
Control Variable
Occupancy Mode
BMS Comm Loss Occupancy
Fallback Mode
Occupancy Schedule Day
Mode
Start Time: 00:00
Stop Time: 00:00
Occupied Timed Override
Enable
Duration
Occupied Auto Mode
Enable
Deadband
Unoccupied Start Enable Modes
Cooling
Heating
Dehumidification
Default
Min.
BMS, Digital Input, Schedule, Always Occ,
BMS
BMS Last Known, Digital Input, Schedule,
BMS Last Known
Monday, Tuesday, Wednesday, Thursday, Friday,
Monday
Occupied
Occupied, Unoccupied, Schedule
06:00 AM
12:00 AM
06:00 PM
12:00 AM
Disabled (□)
Disabled (□)
60 min.
0 min.
Disabled (□)
Disabled (□)
4.0 Δ°F
0.1 Δ°F
Enabled (X)
Disabled (□)
Enabled (X)
Disabled (□)
Enabled (X)
Disabled (□)
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Max.
Always Unocc
Occupied, Unoccupied
Saturday, Sunday
11:59 PM
11:59 PM
Enabled (X)
240 min.
Enabled (X)
20.0 Δ°F
Enabled (X)
Enabled (X)
Enabled (X)