Warmhaus Enerwa Plus 3000 H Installation & User Manual

Wall mounted condensing system boilers
Table of Contents

Advertisement

Quick Links

Enerwa Plus 2500 H
Enerwa Plus 3000 H
Enerwa Plus 3500 H
WALL MOUNTED CONDENSING SYSTEM BOILERS
INSTALLATION & USER MANUAL

Advertisement

Table of Contents
loading

Summary of Contents for Warmhaus Enerwa Plus 3000 H

  • Page 1 Enerwa Plus 2500 H Enerwa Plus 3000 H Enerwa Plus 3500 H WALL MOUNTED CONDENSING SYSTEM BOILERS INSTALLATION & USER MANUAL...
  • Page 2 EnerwaPlus 2500 H EnerwaPlus 3000 H EnerwaPlus 3500 H...
  • Page 3: Table Of Contents

    INDEX FOR USERS ................27 DEAR WARMHAUS CUSTOMER ........... 4 1.1. GENERAL WARNINGS ..............4 3.1. GENERAL WARNINGS FOR USERS ......... 27 1.2. TERMS AND CONDITIONS OF WARRANTY ......4 3.1.1. Use of the Boiler ................27 1.3. BOILER GAS CATEGORIES & DESTINATIONS ......5 3.2.
  • Page 4: Dear Warmhaus Customer

    Incorrect operation of the boiler can cause significant damage. WARMHAUS declares that Enerwa Plus 1800 H - 2500 H - 3000 H - 3500 H boilers comply with the essential requirements of the following directives: For Warmhaus wall-mounted boilers; commissioning, adjustment,...
  • Page 5: Boiler Gas Categories & Destinations

    1.3. BOILER GAS CATEGORIES & DESTINATIONS Gas categories for Warmhaus boilers has been applied on CE certification on SZU Test / BRNO given bellow; - the appliance category(ies) in relation to the direct countries of destinationhas been spesified EN 15502-1; GAR Certificate product ID Nr. CE-1015CT0706 :18 - EN 437+A1:2009, Codes for the representation of gases - the country(-ies) of destination, in accordance with EN ISO 3166-1;...
  • Page 6: Gas Leakages

    WARMHAUS A.Ş. reserves the right to make all kinds of technical and commercial modifications without notice, and disclaims any liabilities arising out of printing and spelling mistakes. IMPORTANT INFORMATION It is a statutory requirement that all gas appliances are installed by competent persons, in accordance with the gas safety (installation and use) regulations (current edition).
  • Page 7: Installation Personnel Section

    2. INSTALLATION PERSONNEL SECTION 2.1. CONTENTS OF THE PACKING BOX Warmhaus is delivered in two boxes as Boiler and Flue Set Box. The Boiler box contains the materials listed below and the small box contains I. Installation Scheme (Figure 1) II.
  • Page 8: Boiler Installation Rules

    7) Condensate Drainage Line Reducing Setting Button 8) Sediment-Air Separator Discharge 17) Exhaust gas/Flue outlet 9) Heating/Domestic Hot Water MODE 18) Hanger plate Button 10) Heating Temperature Increasing Setting Button, Figure 5 Enerwa Plus H boiler dimensions and connections warmhaus.com...
  • Page 9: Mounting Of The Boiler To Wall And Selection Of Installation Place

    In case capacity of the appliance is not exceeded. of failing to fulfil these conditions, combi shall not be commissioned by Warmhaus Authorized Services. 2.2.8. Heating and Domestic Hot Water Installations Radiator and ground heating installation shall be configured in accordance...
  • Page 10: Hydraulic Installation Rules

    Figure 7 Combi bottled gas connection the critical line pressure loss. Warmhaus recommends the pump complying with the European Energy Efficiency Directives (ErP) given in Figure 38 which is provided as optional , in order to achieve a good performance and energy 2.3.
  • Page 11: Checks For Start-Up Of The Boiler

    3 m. SECTION 2 - INS Start-up of the boiler must be carried out by Warmhaus Authorized Service in order to commence warranty of the boiler. Preliminary preparations shall have been performed prior to request for authorized service appointment.
  • Page 12: Fittings Required For Operation Of The Boiler And Heating System

    Min Ø 19 mm insulation water connection pipes for earthing. Inner pipe WARMHAUS A.Ş. cannot be held responsible for any damage or loss to Minimum 30 mm 75 mm flusher individuals or property arising from failing to provide earth connection of...
  • Page 13: Optional Controls: Room Thermostat, Outside Temperature Sensor, Connections And Installation

    3rd class multiple poled disconnected should devices and they must be Warmhaus approved. be envisaged on the same grid. Contact our Authorized Warmhaus Service for replacement of the cable. Please follow instructions of use for placement of outside Temperature Sensor.
  • Page 14: Sample Installation Scheme

    2.5. SAMPLE INSTALLATION SCHEME Single Boiler Scheme Figure 20 Enerwa Plus H Single Boiler with 1 High Temperature Zone + Hot Water Storage Tank System Scheme Example. warmhaus.com...
  • Page 15: Sample Installation Scheme

    2.6. SAMPLE INSTALLATION SCHEME Cascade System Scheme Figure 21 Cascade System with Enerwa Plus H Boilers and 1 Radiator (High Temperature) Circuit and Hot Water Storage Tank Scheme Example warmhaus.com...
  • Page 16 Figure 23 MLC 27 and MLC30 Electrical Connection Diagram for Enerwa Plus H Boilers with Cascade System and 1 Low Temperature (Underfloor Heating) Zone System warmhaus.com is document will have to destroy, on his own responsibility, earlier versions and eventual copies. The content of this document is Bertelli &...
  • Page 17: Remote Control & Control Accessories (Optional)

    It is the sensor which measures the outside air temperature and inform maximum flow water temperature to the boiler. A single boiler heating 153.11.660.600001 WDHS-01-Outside Sensor system or cascade heating systems must be used with one Outside Sensor to save fuel. Look at The Technical Catalogue for detailed information. warmhaus.com...
  • Page 18: Combi Flue Connections

    Combi should only be installed with original Warmhaus air suction and exhaust gas discharge device made of plastic material. Plastic channels cannot be installed without suitable protection against UV and weather conditions to distances over 40 cm and exteriors.
  • Page 19 For that reason, a housing installation should not be performed at places where this vapour may cause should be installed in the wall for lining the internal surface of channel discomfort. wherein the output pipe passes through the wall, particularly for thick walls. warmhaus.com...
  • Page 20: Peripheral Distances Of Flue Output Connections

    Interior Wall Connection Bolt (7) into the flue terminal. performed. • Make required flue selection for the flue connection to be made externall and installation place of the combi. If the standard flue set warmhaus.com...
  • Page 21 Standard Flue Set Pipe (L2) e- Additional 45° Bend For security purposes, combi suction / f- Standard Flue Set Pipe (L3) discharge flue should not blocked even temporarily. Figure 39 III. Single 90° and two 45° bended sample flue installations warmhaus.com...
  • Page 22: Installation With Vertical Flue Sets (Ø 60/100 Mm)

    Figure 42 Hermetic flue type installation sample Correct in implementation. ATTENTION! For C1 boilers the terminal outlet from separete combustion and air supply circuits shall fit inside a square of 50 cm for boilers with a heat input up to 70 kW. warmhaus.com...
  • Page 23 (80 mm) INTAKE EXHAUST TOTAL HORIZONTAL LENGHT : A+B = 30 m Figure 44 Horizontal Air-Flue Lengths Min.40 mm FLUE OUTLET 102 mm Figure 43 INTAKE TOTAL VERTICAL LENGTH: A+B =32 m warmhaus.com Figure 45 Vertical Air and Horizontal Flue Lengths...
  • Page 24 (Ø60/100) Condensed Flue Extension 153.11.660.600015 L=1000 mm (Ø60/100) Condensed Flue Extension 153.11.660.600016 L=2000 mm (Ø60/100) Condensed 45° Elbow 153.11.660.600017 (Ø60/100) Condensed 90° Elbow 153.11.660.600018 L=170 mm (Ø60/100) Condensed Vertical Adapter 153.11.660.600019 L=130 mm Stand-Off Kit Product Name Product Code Stand-Off Kit 151.11.04.003 warmhaus.com...
  • Page 25 153.11.660.600093 L=2000 mm 153.11.660.600094 Ø80 Twin Flue Bend (90°) 153.11.660.600095 Ø80 Twin Flue Bend (45°) 153.11.660.600099 Ø80 Interior Wall Rosette 153.11.660.600098 Ø80 Exterior Wall Rosette 153.11.660.600100 Ø80 Flue Vertical Outlet Adapter with Condensate Trap 153.11.660.600097 Ø80 Vertical Flue Kit warmhaus.com...
  • Page 26: Recommendations Of Plume Kit Installation

    150 mm passageway. MIN. 3. If a terminal is less than 2 metres above Figure 46 Installation Position of Plume Displacement Set to a balcony, above ground or above a Window or Door warmhaus.com...
  • Page 27: For Users

    Call gas company or authorized service (See 1.3 Gas leaks) Follow the rules specified below: Start-up of your boiler must be carried out by Warmhaus Authorized • Do not clean the outer body of the boiler while the boiler is operating, service in order to maintain warranty scope of your boiler.
  • Page 28: Operation In Winter Mode

    HEAT: Heating; HSW: Hot Domestic Water is energized, the temperature value is the temperature of the water in the system. RESET: Used for restarting the combi boiler and eliminating the fault in case of a fault. MODE: Used for Winter/Summer/OFF mode setting. warmhaus.com...
  • Page 29: On/Off/Stand-By Positions

    {If you have an underfloor heating system, the temperature adjustable by the Heating temperature setting buttons (3) will be limited to the maximum temperature value (e.g. Maximum 47 °C) as your boiler will have been set to “Low Temperature Operation” by the Authorized Service} warmhaus.com...
  • Page 30: Operation In Summer Mode (If A Boiler Is Fitted)

    3.2.10. Use with Room Thermostat (Optional) The boiler is readily suitable for connection of ambient thermostats with remote control sold as optional set. All Warmhaus thermostats can be connected with dual-wired cable. Read the operation and installation instructions in the accessories set. You can control your boiler from anywhere (e.g.
  • Page 31: Trouble Shooting

    The boiler does not operate, E10 > Heating system RETURN 1-) Restart the boiler by pushing RESET button. E 10 sensor is faulty error code blinks temperature sensor is faulty 2-) Call the authorized service if fault remains unsolved. warmhaus.com...
  • Page 32 3-) Check the cabling between the boiler and thermostat, and fix connection interrupted communication error any interruptions, no 19 symbol will appear on the display if the connection is successful 4-) Call authorized service to re-connect the room thermostat (Opentherm). warmhaus.com...
  • Page 33 The boiler does not operate, > Gas Supply Pressure windstorm to stop, then restart the boiler by pushing RESET E 84 (assumed) low gas supply pressure E84 error code blinks > Ignition fault button. 2-) Call Authorized service if the fault remains unsolved. warmhaus.com...
  • Page 34 2-) Call the authorized service if fault remains unsolved. The boiler does not operate, > Boiler electronic 1-) Restart the boiler by pushing RESET button. E 99 General fault E99 error code blinks equipment fault 2-) Call the authorized service if fault remains unsolved. warmhaus.com...
  • Page 35: Recommendations For Economical Use Of The Boiler

    3.5. MATTERS TO PAY ATTENTION FOR GUARANTEE CONDITIONS This warranty provided by WARMHAUS does not include fixing or eliminating faults caused by use of the appliance for purposes other than intended use as well as the conditions specified below:...
  • Page 36 Gas Adaptive (*): This boiler fitted with gas/air ratio controls. Gas and air ratio control settings must not be changed un autorised persons. The gas valve calibration method is explained on service manual and has to be done by Warmhaus official service.
  • Page 37 Product Fiche & ErP Data Warmhaus Enerwa Plus H boilers granted ErP & Product Fiche for Warmhaus boilers has been tested and reported on SZU Test / BRNO given bellow; PRODUCT FICHE (according to EU regulation No 811/2013 and 814/2013) Enerwa Plus Enerwa Plus...
  • Page 38 warmhaus.com...
  • Page 39 warmhaus.com...
  • Page 40 warmhaus.com...
  • Page 41 Enerwa Plus 2500 H Enerwa Plus 3000 H Enerwa Plus 3500 H warmhaus.com...
  • Page 43 All descriptions and illustrations provided in this document have been carefully prepared but we reserve the right to make changes and improvements in our products which may affect the accuracy of the information contained in this leaflet. All goods are sold subject to our standard Conditions of Sale which are available on request.
  • Page 44 Enerwa Plus 2500 H Enerwa Plus 3000 H Enerwa Plus 3500 H...