Warmhaus Minerwa 25 System IE Installation & Service Manual

Warmhaus Minerwa 25 System IE Installation & Service Manual

Condensing system boiler
Table of Contents

Advertisement

MinerWa 25 System – IE
CONDENSING SYSTEM BOILER
INSTALLATION & SERVICE MANUAL

Advertisement

Table of Contents
loading

Summary of Contents for Warmhaus Minerwa 25 System IE

  • Page 1 MinerWa 25 System – IE CONDENSING SYSTEM BOILER INSTALLATION & SERVICE MANUAL...
  • Page 2 warmhaus.com...
  • Page 3 The Benchmark Scheme Warmhaus is a licensed member of the Benchmark Scheme which aims to improve the standards of installation and commissioning of domestic heating and hot water systems in the UK and to encourage regular servicing to optimise safety, efficiency and performance.
  • Page 5: Table Of Contents

    EXTERNAL CONTROL CONNECTION / LOW VOLTAGE INSTALLATION ..27 5.17. DHW PLATE HEAT EXCHANGER REPLACEMENT 3.16.3. EXTERNAL CONTROL CONNECTION / SPLAN WIRING DIAGRAM ....28 (FOR COMBI BOILERS ONLY) ............52 FAULT CODES ................... 53 3.16.4. EXTERNAL CONTROL CONNECTION / YPLAN WIRING DIAGRAM ....29 warmhaus.com...
  • Page 6: Introduction

     Warmhaus. This safety warning indicates that severe and life-threatening • Do not modify our flue system, and always use only the Warmhaus personal injury may occur. approved flue with this appliance. • Ensure Warmhaus original flue components including seals and gaskets ATTENTION are used for the installation of this appliance.
  • Page 7 • ECTI - National rules for electrical installations • Irish Standard IS 10101:2020. • IS813-2017 - Domestic Gas Installations WARMHAUS A.Ş. reserves the right to make all kinds of technical and commercial amendments without giving information and rejects all responsibilities depending on misspelling. 1015...
  • Page 8: Technical Specification

    Dimensions (H x W x D) 595 x 379 x 260 Net Weight Packaged Weight Clearances Above Casing Clearances Below Casing Clearances Front - Operational Clearances Front - Servicing Clearances Right Hand Side Clearances Left Hand Side Sound Level NOx Classification warmhaus.com...
  • Page 9: Product Identification

    Boiler Plus e.g. Smart stat, Boiler Plus compliant room/programmable room stat. TRVs should also be installed in a minimum of sleeping areas and as best practice on all radiators with the exception of the room or area where the room thermostat is installed. warmhaus.com...
  • Page 10: Pre-Installation

    2. PRE-INSTALLATION 2.1. PACKING CONTENTS The Warmhaus Boiler is supplied in a box which contains the materials listed below: 1. Wall Mounting Template 5. Warranty Card 2. Mounting Bracket 6. Hardware Pack 3. Valve Set 7. Installation/Servicing Instructions 4. External Control Relay 8.
  • Page 11: Location Of Boiler / Clearance

    Installations in rooms containing baths or showers Warmhaus MinerWa 25 System – IE boiler has an IPX5D rating Any switch or appliance external controls using mains electricity should not be in reach of any person using a bath or shower.
  • Page 12: System Requirements

    warmhaus.com...
  • Page 13: Flue Terminal Position

    From an opening in the car port into the building 1200 Vertically from a terminal on the same wall 1500 Horizontally from a terminal on the same wall From a structure on the roof Please see ref AP233 Above the highest point of intersection with the roof warmhaus.com...
  • Page 14: Installation

    Make sure the boiler is correctly located on the mounting bracket and that the boiler is level and straight. warmhaus.com...
  • Page 15: Appliance Connections

    3.7. APPLIANCE CONNECTIONS The Warmhaus Minerwa boiler is supplied with a hardware pack containing isolation valves and a connector pipe for the installer to connect to the boiler unit. The hardware pack supplied is: • Flow – 22 mm isolation valve (compression) •...
  • Page 16: Filling Appliance & Adding Inhibitor

    ADDING INHIBITOR  CAUTION The inhibitor used in the system with your Warmhaus boiler must not cause damage to any materials within the boiler e.g. stainless steel, copper, brass and any other composite material. If the boiler is installed in areas such as leisure accommodation, then the...
  • Page 17: Installing The Flue System

    • Place the flue elbow (90°) (1) press down and tighten the screw (6) to approved to work with any Warmhaus appliances – see secure the flue elbow (see picture B) below our list of standard products: •...
  • Page 18: Installation With Vertical Flue Sets (Ø60/100 Mm)

    The vertical flue terminal can be fitted to both flat and pitched surfaces. Flue Data  WARNING Warmhaus flue pipe technical specification: Vertical Termination: • Maximum length = 11 meters including the bend or adaptor connected directly to the boiler.
  • Page 19 L2 = 0.5 m. (45° bend equivalent length) L3 = 2.0 m. L4 = 0.5 m. (45° bend equivalent length) L5 = 1.0 m. L6 = 1.5 m. L Total =6.3 m. 6.3 m. < Lmax = 11 m. Correct in implementation. warmhaus.com...
  • Page 20: Concentric Flue Kits For Condensing Boilers (Ø60/100 Mm)

    153.11.660.600114 (Black) (Ø60/100) Condensing 153.11.660.600018 (White) 90° Elbow L=170 mm 153.11.660.600121 (Grey) (Ø60/100) Condensing 153.11.660.600115 (Black) Vertical Adapter 153.11.660.600019 (White) L=130 mm 153.11.660.600122 (Grey) Flat Roof Outlet Part Pitched Roof Outlet Tile A = 500 x 500 mm 153.11.660.600124 153.11.660.600125 warmhaus.com...
  • Page 21: Plume Displacement Kits Ø60 Mm

    • Under car ports we recommend the use of the plume must be a minimum of 150mm from any opening windows or displacement kit. doors) • The terminal position must ensure the safe and nuisance - free dispersal of combustion products. warmhaus.com...
  • Page 22: Condensate Connection

    25 mm min below grating but above water level; end cut at 45 ° 6 - Minimum internal diameter 19 mm 7 - Pipe size transition 8 - Minimum internal diameter 30 mm 9 - Water/weatherproof insulation 10 - Fit drain cover/leaf guard warmhaus.com...
  • Page 23 7 - Pipe size transition 8 - Minimum internal diameter 30 mm 9 - Water/weatherproof insulation 10 - Fit drain cover/leaf guard Note – Any external pipe work should be insulated, pipe cut at 45 degrees and a drain/ leaf guard fitted. warmhaus.com...
  • Page 24 4 43 mm 90° male/female bend 5 External rainwater pipe into foul water 6 External air break 7 Air gap 8 68 mm PVCu strap on fitting 9 Minimum internal diameter 19 mm 10 Minimum internal diameter 30 mm 11 End cut at 45° warmhaus.com...
  • Page 25 7 Hole depth 400 mm minimum by 300 mm diameter 8 Minimum internal diameter 19 mm 9 Pipe size transition point 10 Minimum internal diameter 30 mm 11 Water/weatherproof insulation warmhaus.com...
  • Page 26: Minerwa 25 System - Ie Wiring Diagram

    3.16. MINERWA 25 SYSTEM – IE WIRING DIAGRAM WIRING DIAGRAM  RISK OF ELECTRIC SHOCK  warmhaus.com...
  • Page 27: External Control Connection / Low Voltage Installation

    If your external controls have a 240 V output then please use our 240 V relay connector supplied with the boiler. To connect your low voltage external control, remove the green link wire and connect your two external control cables to the two green wires on the terminal connector. warmhaus.com...
  • Page 28: External Control Connection / Splan Wiring Diagram

    BOILER WITHOUT TIMER MODEL SPLAN Wiring Guide: The Warmhaus Minerwa boiler must have clean contact connections and must not have mains voltage connected to the room stat connections on our terminal connector, therefore if the system configuration is an SPLAN please follow the above image to ensure that 240v voltage will not be applied to the room stat connections on the boiler.
  • Page 29: External Control Connection / Yplan Wiring Diagram

    BOILER WITHOUT TIMER MODEL YPLAN Wiring Guide: The Warmhaus Minerwa boiler must have clean contact connections and must not have voltage connected to the room stat position on our terminal connector, therefore if the system configuration is a YPLAN you...
  • Page 30: Commissioning

    Attention: This procedure must be applied by authorized persons and valid for only condensing boiler. Attention: The parameters as indicated DO NOT CHANGE should not be adjusted / touched by any official document supplied by Warmhaus R&D. Press the RESET and CH (-) button simultaneously...
  • Page 31: Parameters

    4.1.2. PARAMETERS Transparent Parameters Menu (TSP) Designation : All Warmhaus Wallhung Boilers Object Type-model(s) Burner Control Transparent Parameter List MINERWA 25 Parameter no. Parameter Value Field Default Hydraulic system 0 = Instantaneous 1 = Thermostat storage tank 0 – 3...
  • Page 32 Transparent Parameters Menu (TSP) Designation : All Warmhaus Wallhung Boilers Object Type-model(s) Burner Control Transparent Parameter List MINERWA 25 Parameter no. Parameter Value Field Default Selection of boiler power 0 = 24 kw 1 = 28 kw 2 = 33 kw...
  • Page 33 Transparent Parameters Menu (TSP) Designation : All Warmhaus Wallhung Boilers Object Type-model(s) Burner Control Transparent Parameter List MINERWA 25 Parameter no. Parameter Value Field Default 184 = NG Maximum power fan speed ( P32 x 25 + 2000 rpm )
  • Page 34 Transparent Parameters Menu (TSP) Designation : All Warmhaus Wallhung Boilers Object Type-model(s) Burner Control Transparent Parameter List MINERWA 25 Parameter no. Parameter Value Field Default Relay configuration 1 LC27 0 = Not used 1 = Remote alarm normally open 2 = Remote alarm normally close 3 = Zone valve 0 –...
  • Page 35 Transparent Parameters Menu (TSP) Designation : All Warmhaus Wallhung Boilers Object Type-model(s) Burner Control Transparent Parameter List MINERWA 25 Parameter no. Parameter Value Field Default Fan supply reduction @min power (up to180Vac) 0 – 15 Fan selection (not use) 0 = EBM 1 = B&P...
  • Page 36: Parameter Information

    As this is the property of Warmhaus Isıtma ve Sogutma Sistemleri San. Tic. A.Ş. It must not be passed on to any person not authorized by Warmhaus Isıtma ve Sogutma Sistemleri San. Tic. A.Ş or be copied or otherwise utilized by anybody without expressed written permission.
  • Page 37: Calibration

    Nominal Value 10.4 Ignition Power= P01 Permitted Tolerance Value 10.5 - 10.0 5.0 - 5.9 45—80 10-20 48 - 78 Nominal Value 10.3 Minimum Power=P00=LO Permitted Tolerance Value 10.0 - 10.5 5.0 - 5.9 0-10 8-15 25 - 57 warmhaus.com...
  • Page 38: Auto Calibration

    Wait until the approval circle complete on the LCD and release buttons. As this is the property of Warmhaus Isıtma ve Sogutma Sistemleri San. Tic. A.Ş. It must not be passed on to any person not authorized by Warmhaus Isıtma ve Sogutma Sistemleri San.
  • Page 39: Manual Calibration

    As this is the property of Warmhaus Isıtma ve Sogutma Sistemleri San. Tic. A.Ş. It must not be passed on to any person not authorized by Warmhaus Isıtma ve Sogutma Sistemleri San. Tic. A.Ş or be copied or otherwise utilized by anybody without expressed written permission.
  • Page 40: Esf (Easy Start Up Function)

    Wait until the approval circle complete on the LCD and release buttons. JUST AFTER RELEASE BUTTONS then Press the MODE button within 3 seconds. If the MODE is not pressed within 3 seconds the boiler will turn to the OFF state. warmhaus.com...
  • Page 41 If the OT thermostat is connected and there is heat demand the boiler will go on burning." "If the boiler will not be used in winter mode, be sure that the boiler is in Summer or OFF mode after the ESF function. Change the working state by using the ""Mode"" button." warmhaus.com...
  • Page 42: Information Menu Access

    Object Type-model / Technical data Mark (s) of conformity Procedure Info Menu MinerWa 25 System – IE granted by Warmhaus R&D Pos No Operation Description GB Attention: This procedure must be applied by authorized persons. Press the RESET and CH (+) button simultaneously.
  • Page 43: Deaeration Mode

    Wait until the approval circle complete on the LCD and release buttons. As this is the property of Warmhaus Isıtma ve Sogutma Sistemleri San. Tic. A.Ş. It must not be passed on to any person not authorized by Warmhaus Isıtma ve Sogutma Sistemleri San.
  • Page 44: Pre-Commissioning Checklist

    Ensure that all flue joints are correctly made and sealed and check the flue The gas rate must be carried out in accordance to the current gas working is suitably supported as per the manufacturer’s instructions. practices. warmhaus.com...
  • Page 45: Circulation Pump Rotation

    If the App calculator is proven to be accurate and can be used as a trusted source then Warmhaus will be happy to accept the results given by this method. When comparing the gas rate data from your test please use the DHW figures on the data badge or the stated gas rate in the technical data chart is this manual as the reference and not the CH data.
  • Page 46: Gas Conversion From Ng (G20) To Lpg (G31)

    LPG=G31 As this is the property of Warmhaus Isıtma ve Sogutma Sistemleri San. Tic. A.Ş. It must not be passed on to any person not authorized by Warmhaus Isıtma ve Sogutma Sistemleri San. Tic. A.Ş or be copied or otherwise utilized by anybody without expressed written permission.
  • Page 47: Gas Conversion From Lpg (G31) To Ng (G20)

    LPG=G31 As this is the property of Warmhaus Isıtma ve Sogutma Sistemleri San. Tic. A.Ş. It must not be passed on to any person not authorized by Warmhaus Isıtma ve Sogutma Sistemleri San. Tic. A.Ş or be copied or otherwise utilized by anybody without expressed written permission.
  • Page 48: Co/Co2 Combustion Check

    Service Mode and no further flue Integrity checks then please run Auto adjustments are required. Calibration /please follow Auto Calibration procedure/ warmhaus.com...
  • Page 49: Servicing & Part Replacement

    Deareation mode. local governing gas body or regulator for essential checks when working on a gas appliance and Warmhaus require that you carry out the following checks as well as your industry required safety checks e.g. 26/9 checks.
  • Page 50: Flue Thermistor Replacement

    Please follow the step listed in replacement of components FINAL STAGE. 6. Reassemble the above parts in reverse order. 7. Restore the gas and electric supply to the boiler. 5.6. IGNITION ELECTRODE REPLACEMENT Please follow the step listed in replacement of components FINAL STAGE.  CAUTION warmhaus.com...
  • Page 51: Flow & Return Thermistor Replacement

    5. Install the new pump head and secure the 4 x pump head securing screws. 6. Reconnect the electrical connector plugs to the pump. 7. Re-pressurize the boiler and bleed all excess air. Please follow the step listed in replacement of components FINAL STAGE. warmhaus.com...
  • Page 52: Outlet Manifold Replacement

    8. Check the PRV terminal (if possible) has not been affected by the PRV replacement. 9. Re-pressurize the boiler and bleed all excess air. Please follow the step listed in replacement of components FINAL STAGE. 5.16. DHW Flow Sensor Replacement (for combi boilers only) warmhaus.com...
  • Page 53: Fault Codes

    PWM cable, pump main supply connector, pump main connector, measure voltage from connectors 8-) Check if there is air in the heat exchanger or system, remove air if any by activating the Deareation mode 9-) Check heat exchanger water path 10-) Reset & restart boiler warmhaus.com...
  • Page 54 E12 error code flashing on temperature sensor in 2-) Check Domestic heating (hot?) water temperature sensor resistance the screen storage tank faulty 3-) Check cabling and connectors between NTC and board 4-) Reset & restart boiler   warmhaus.com...
  • Page 55 System inhibitor concentration has been checked and System inhibitor concentration has been checked and appropriate action taken, in accordance with BS 7593 appropriate action taken, in accordance with BS 7593 and boiler manufacturers’ instructions. * and boiler manufacturers’ instructions. * Comments: Comments: Signature: Signature: warmhaus.com...
  • Page 56 Warranty Card Warmhaus Boilers Warranty Registration Form Please complete all details below Installer Details Homeowner Details Name ___________________________________ Name ___________________________________ Address ___________________________________ Company Name ___________________________________ Account No ___________________________________ ___________________________________ Phone Number ___________________________________ Eircode ___________________________________ Email ___________________________________ Phone Number ___________________________________ RGI Number...
  • Page 58 MinerWa 25 System – IE GAS EMERGENCIES If you smell gas call Gas Networks Ireland 24 hour emergency line immediately or 1850 20 50 50. Don't assume somebody else has reported the smell. Carbon monoxide information For further Information on carbon monoxide call; 1850 79 79 79 The carbon monoxide phone line is open Monday- Friday.