Download Print this page

Specifications; Ordering Information - Honeywell V4043A Manual

Motorized valves

Advertisement

V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED VALVES

SPECIFICATIONS

®
TRADELINE
Models
TRADELINE® models are selected and packaged to provide
ease of stocking, ease of handling, and maximum
replacement value. TRADELINE® model specifications are
the same as those of standard models except as noted below.
TRADELINE® Models Available: V8043A,E and V8043E,F
(see Table 1).
Capacity Rating (nominal): (See Table 1)
Straight-through models:
1.0 Cv (.86 kv)
3.5 Cv (3.0 kv) Standard
8.0 Cv (6.9 kv)
Diverting models:
4.0 Cv (3.5 kv) Standard
7.0 Cv (6.0 kv)
Additional Feature: End switch enclosure included.
Standard Models
Models:
V4043: line voltage, straight-through valves.
V4044: line voltage, 2-position diverting valves.
V8043: low voltage, straight-through valves.
V8044: low voltage, 2-position diverting valves.
See Table 1.

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
60-2133—10
Electrical Ratings
(See Table 1 for Voltage of Specific Models):
Voltage
Amperes
24
0.320
100
0.087
120
0.080
208
0.044
a
Maximum five V8043 Zone Valves per 40 VA transformer.
Changeover Aquastat® Control: 120V, 3.0 A with 10.0 A
inrush.
End Switch: 120 V, 4.4 A running with 26.4 A inrush (60 Hz).
Pilot duty 50 VA at 24 V.
Humidity Rating: 5-95% RH (non-condensing).
Atmosphere: non-corrosive, non-explosive.
Timing:
V4043 and V8043: Open or close in 15 seconds maximum.
V4044 and V8044: Divert flow in 30 seconds maximum.
Dimensions: See Fig. 1.
Manual Opener: Manual opener (on all except the straight-
through, normally open valves) allows opening the valve in
case of power failure. Valve returns to automatic position
when power is restored.
2
Voltage
Amperes
a
220
240
277
0.042
0.040
0.037

Hide quick links:

Advertisement

loading

This manual is also suitable for:

V4043bV4044aV8043aV4044bV8043bV8043e ... Show all