Press ENTER to save new address.The address
field should stop blinking.
Press T1 (MENU) to go back to the previous
menu.
NOTE: When the MODBUS address is
changed, the High Pressure CO2 controller
needs to be rebooted.
3.1.2.4

Versions

The High Pressure CO2 controller and Visograph ver-
sions are also shown on the Controller Info screen.
To see the High Pressure CO2 controller version,
please see the Visograph Section of the Status screen.
3.2

MODBUS Termination

If the High Pressure CO2 controller is located at the
physical end of the MODBUS network, install the MOD-
BUS termination block (P/N 537-2711).
16 • High Pressure CO2 Controller Installation and Operation Manual
026-1731 Rev 0 01-DEC-2014