Table of Contents 1 OVERVIEW ................................... 1 1.1 T CO2 C I/O P ....................1 RESSURE ONTROLLER OINTS 1.2 I ..........................2 NDEPENDENT YSTEM ONTROL 2 HARDWARE SETUP..............................3 2.1 C ................................3 ONNECTIONS 2.2 I ..............................4 NPUTS AND UTPUTS 2.3 T ............................
Page 6
7.1 L ............................28 RESSURE PERATION 7.1.1 Normal Operation ..............................28 7.2 H ............................28 RESSURE PERATION 7.2.1 Normal Operation ..............................28 7.3 S ................................. 29 ENSOR AILURE 7.4 E ........................29 MERGENCY HUTDOWN NABLE NPUT 8 VALVE CALIBRATION FEATURE ........................30 9 ALARMS..................................
Overview The High Pressure CO2 Controller I/O The High Pressure CO2 controller (P/N 818-9010) application is a standalone controller that operates the Points High Pressure Valve (HPV) and the Bypass Gas Valve (BGV) in a Booster Transcritical CO2 system. The board has 6 analog inputs and 11 digital in-...
Independent System Control The High Pressure CO2 controller can control the HPV and BGV in a refrigeration Booster Transcritical CO2 System. However, the High Pressure CO2 con- troller is designed to interface with an E2. Network- ing the High Pressure CO2 controller to a central controller also allows you to view status on E2 and UltraSite32 Site Manager status screens, report alarms, and log point values.
Hardware Setup Figure 2-1 - High Pressure CO2 Controller Connections Connector Description Connector for 24VAC/DC power supply Analog inputs (Pb1 - Pb6, PbC) Additional power: +5VDC, +12VDC, Common (-) Analog outputs (Out1 - Out4, Common) 24VAC/DC digital inputs: DI1 - DI11, Common (-) Connector for remote terminal (VISOGRAPH), maximum 1 terminal per controller.
Connector Description Digital relay outputs 4 NO relays, 2 common Digital relay outputs 4 NO relays, 2 common Table 2-1 - Connections and Descriptions Inputs and Outputs Input Type of Description Number Input Supply Reference “-“/Common power (24VAC or 24VDC) Configurable analog input 1 (NTC, PTC, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 - 5V, DI) Configurable analog input 2 (NTC, PTC, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 - 5V, DI) Configurable analog input 3 (NTC, PTC, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 - 5V, DI)
Page 11
Input Type of Description Number Input Digital input 3, 24VAC/DC Digital input 4, 24VAC/DC Digital input 5, 24VAC/DC Digital input 6, 24VAC/DC Digital input 7, 24VAC/DC Digital input 8, 24VAC/DC Digital input 9, 24VAC/DC DI10 Digital input 10, 24VAC/DC DI11 Digital input 11, 24VAC/DC Digital Reference “-”...
(24VAC/DC) via software External power 24VAC/DC ±20% Number of parameter) Inputs: Number of Type of analog NTC Emerson Retail Solutions Inputs: input: (-50T110°C; 10KΩ±1% at 25°C) (configurable PTC Emerson Retail Solutions Digital input 100ms (in any case it depends on via software (-55T115°C;...
2.3.3 Analog Outputs 2.3.4 Digital Outputs Type: Non opto-insulated internal power Type: Relays with NO contacts Number of Number of Outputs: Outputs: Type of analog 4 configurable outputs 0-10VDC Type of analog Relays with normally open output: 4-20mA (Out1 - Out4) output: contact (configurable...
2.3.6 Wiring Diagrams Figure 2-3 - Wiring Diagrams NOTE: To ensure control in case of a power failure, it is recommended that a UPS be used on the High Pressure CO2 controller. • 9...
2.3.7 Electrical Specifications 2.3.9 USB-Ethernet Adapter The IPS range of programmable controllers can be 24VAC +10/-15%, 50/60Hz, 20 - connected to a computer via an external adapter. This Power Supply: 36VDC adapter must be used in the processing environment for the application download in the controller. This From 30VA (VAC), From 25W Consumption: adapter is not set up for fixed or continuous connec-...
2.4.2. Wire Types and Maximum Neither side of the secondary should be connected to ground. Also, do not connect the center tap (if pro- Distances vided on the transformer) to ground. The entire sec- ondary of the transformer should be isolated from any For powering I/O boards, use only the listed wire ground.
The MODBUS Network If the recommended cable is not available in your area, be sure the wiring meets or exceeds the following specs: Although the High Pressure CO2 controller can Shielded? operate as a stand-alone controller, it relies on an E2 unit for advanced features such as remote dial-in/dial- Twisted Pair Conductor Type...
3.1.2. Network Addressing - Visograph The network address makes a board unique from other boards on the network of the same type. This allows the site controller to find it and communicate with it easily. The network address of the High Pressure CO2 controller is set using add-on devices called visographs (P/N 818-9002).
3.1.2.2. Visograph Navigation • Four status menu items are available to choose from within the status menu. • Press corresponding button along the bottom (T1-T8) to navigate to desired item. Figure 3-5 - Configuration Screen Highlight General Config and press the ENTER key (T3).
Press ENTER to save new address.The address field should stop blinking. Press T1 (MENU) to go back to the previous menu. NOTE: When the MODBUS address is changed, the High Pressure CO2 controller needs to be rebooted. 3.1.2.4 Versions The High Pressure CO2 controller and Visograph ver- sions are also shown on the Controller Info screen.
Inputs and Outputs Setup Inputs Setup The High Pressure CO2 application has the ability to assign all inputs to be any of the possible options for an analog input in the application. The analog inputs will have offsets available while the digital inputs will have a polarity option.
Page 24
Figure 4-1 - Analog Input Connectors CAUTION: Any inputs that are powered with a voltage that differs from that supplied by the High Pressure CO2 controller (+12V or +5V) must be powered separately with another transformer in order to prevent the inputs from mal- functioning or being damaged.
Page 25
Terminal Number on Name Connector Probe Input 6 Temperature Common Transducer/Analog Output Common Analog Output 3 Analog Output 4 Table 4-2 - Analog Input Connector Terminals The digital inputs are located on the corresponding connector terminal below. Pay attention to the input commons as they are share on terminal 31: Digital Common (-) and the digital inputs are voltage input that can handle 24VAC/DC.
Terminal Number on Connector Name Digital Input 7 Digital Input 8 Digital Input 9 Digital Input 10 Digital Input 11 Digital Common Table 4-3 - Digital Input Connector Terminals Outputs Setup The High Pressure CO2 application can assign any output to one of the available relay outputs, which have both delays and polarity configuration definable by a user from the local display and E2.
Page 27
nal 40 and 41 (C) for relay 1 through 4. Figure 4-3 - Relay Output Connectors The analog outputs are located on the same connector terminal as the controller power supply. Pay attention to the analog outputs commons as they are shared on terminal 14: Voltage Common (-). Figure 4-4 - Analog Output Connectors •...
High Pressure CO2 Controller Status LED When a High Pressure CO2 controller board is powered up, the operating status of the board can be determined by observing its status LEDs. Figure 5-1 - LED Locations second (blink twice as fast). When the High Pressure CO2 Power On (PWR ON) controller is offline, you can edit the setpoint from the Visograph display.
Software High Pressure Valve Overview Control The high pressure valve (HPV) operates in two The High Pressure CO2 controller application normal-control modes, in Subcritical and Transcriti- controls the operation of the high pressure valve and cal modes. The mode is defined by the control tem- the bypass gas valve in a Booster Transcritical CO2 perature.
Subcritical Parameter Description Default Value 31 DC HPV Mode Setpoint Setpoint for Subcritical and Transcritical mode (87 DF) 3 DDC HPV Mode Hysteresis Control Temperature Hysteresis (5 DDF) 2 DDC HPV Subcool Setpoint Subcool Setpoint in Subcritical Mode (3 DDF) HPV RS-Temp Subcritical proportional band offset 0 DDC...
Page 31
In Transcritical mode, there is a separate PID running. To ensure there is a smooth transition between the subcrit- ical PID and the Transcritical PID, there is a linear-ratio transition algorithm between the two PID's output. This linear-ratio algorithm transition will keep the valve open and allow the Transcritical PID to ramp up and take over.
Heat Reclaim Parameter Description Type Reclaim Setpoint Shift HPV Subcritical Reclaim_Sub 0 DDC Added Reclaim Setpoint Shift HPV Transcritical Reclaim_Trans 0 DBAR Added Table 6-8 - Analog Outputs The Control Temp Selector (CTS) digital input is normally use if there is a gas cooler temperature sensor after a bypass valve to bypass the gas cooler if needed during heat reclaim.
Page 34
BGV Parameter Description Default Value BGV Setpoint Setpoint for Subcritical and Transcritical mode 35 BAR (510 PSI) BGV RS Control Temperature Hysteresis 1.4 BAR (20 PSI) BGV PB (P) Subcool Setpoint in Subcritical Mode 2.75 BAR (40 PSI) BGV INC (I) Subcritical proportional band offset 100 Sec BGV DDER (D)
Safety Operation Parameters for High Pressure and Bypass Gas Valves Refer to Section 7.3, Sensor Failure. Input Description Pressure 2 Receiver Pressure Hi PSI Set High Pressure Receiver Safety Setpoint Hi Hy High Pressure Receiver Safety Setpoint Hysteresis Lo PSI Set Low Pressure Receiver Safety Setpoint Lo Hy Low Pressure Receiver Safety Setpoint Hysteresis...
Control Control Sensor Failure Temp. Condensing Temp. Condensing If a failure occurs on the pressure (P1) at the outlet of the gas cooler, the application: • Uses the back pressure from E2 (Section 4.1, High Pressure Controller Inputs). • If no network backup pressure is available, set the HPV to a fixed opening according to the mode it is in (subcritical or transcritical).
Valve 4. Cal Min Valve % - is the value for when the valve percentage has to equal to or exceed before executing cali- Calibration bration mode IF Cal T Frame value is greater than 0. 5. Direct - is the direction the calibration mode will be initialize the valve fully open or closed.
Alarms The local display and the E2 have the ability to read and display each alarm. Any sensor failure alarms will turn on the relay designated as the General Alarm. For the Shutdown alarm, this is true/active if the enable input is not high from either the physical digital input and/or E2 network if online with E2.
Visograph A Visograph is used as the local display. The screens provide access for setting up and assigning all inputs, and outputs. In addition to the entire parameters’ configura- tion, the user can change the time and date, MODBUS address, baud rate (9600 or 19200), and update the Viso- graph with new screens if needed.
Figure 10-5 - HPV Status Screen the MODBUS address, baud rate, screens update, time and date, Sensor type (Emerson Retail Solutions or Dixell), This screen gives you the HPV status of performance, engineering units, pressure transducer settings, shutdown setpoints, and control input values. To return to the Status delay and the factory default reset.
press T1 + T3 + T8 button together and hold it until you Once the parameter is flashing, press the T3 button or T5 see the Configuration screen. button to change value and press T4 SET again to submit the change. To see additional parameters in the General Configuration Screen: Config screen, press the T8 button (right arrow).
tional Valve Config screen, you can press the T3 button (left arrow) to go back a screen or press the T1 button EXIT to exit back to the main Configuration screen. Valve Configuration Additional Screen: Figure 10-16 - Valve Config Additional Screen Figure 10-13 - Valve Config Additional Screen Valve Configuration Additional Screen:...
Page 43
IO Config Screen: Figure 10-19 Figure 10-21 - IO Config Screen - IO Config Additional Screen Press the T5 button (down arrow) to highlight the parameter you wish to change. Press T4 SET to edit the value. Once the parameter is flashing, press the T3 button or T5 button to change the value and press T4 SET again to submit change.
Figure 10-24 Figure 10-27 XEV20D Config Screen - IO Config Additional Screen Press the T5 button (down arrow) to high the parame- ter you wish to change. Press T4 SET to edit the value. Once the parameter is flashing, press the T3 button or T5 button to change value and press T4 SET again to submit change.
High Pressure CO2 Controller Ranges and Default Setpoint Parameters Setpoints Description Default Range Unit HPV Mode Setpoint Setpoint for Subcritical and Transcritical mode switch -3 to 42 HPV Mode Hysteresis Control Temperature Hysteresis 0 to 20 HPV Subcool Setpoint Setpoint in Subcritical Mode 0 to 100 HTR S Set Reclaim Setpoint Shift-High Pressure Valve-Subcritical...
Page 47
Setpoints Description Default Range Unit Close Rate Rate at which the HPV will close in safety mode 0 to 600 Seconds HPV% Open Fail-SC Valve % open during Subcritical with sensor failure 0 to 100 HPV% Open Fail-TC Valve% open during Transcritical with sensor failure 0 to 100 Valve% minimum opening during low pressure safety HPV% Open Fail-Lo...
XEV20D Setup and Network Connection The XEV20D is a stepper valve driver that can drive a bipolar stepper valve or unipolar stepper valve. It is a dummy voltage chopper constant current driver that will be controlled by the High Pressure CO2 controller through a LAN com- munication network.
Page 49
Figure 12-2 - High Pressure CO2 Device Wiring and Network Connection • 43...
Stepper Valve SAFETY PRECAUTIONS AND Actuator Quick WARNINGS! • Check that the supply voltage is correct Reference Guide before connecting the controller. • Do not expose to water or moisture: use the con- XEV20D troller only within the operating limits and avoid sud- den temperature changes with high atmospheric humidity to prevent condensation from forming.
• 2 configurable valve outputs to drive bipolar or uni- 13.4 Wiring Diagrams polar valves • Pb1/Pb2 configurable analog inputs: NTC/PTC/ 13.4.1 One Valve Configuration Pt1000 • Pb3/Pb4 configurable analog inputs: 4 to 20mA/0 to 5V/Pt1000 • CAN Bus serial line •...
13.5 Valve Connections The following table is a quick reference on the connection mode for valves of different manufacturers: Figure 13-5 - Valve Connections Figure 13-6 - XEV20D 46 • High Pressure CO2 Controller Installation and Operation Manual 026-1731 Rev 0 01-DEC-2014...
13.6 Serial Line - LAN Bus The device can communicate through LAN Bus serial line only when the address is set correctly. The addressing is made through the dip-switch called Address as shown below. The XEV20D address will have to be set to 1 to communi- cate with the High Pressure CO2 controller.
13.7 LED Descriptions The following table contains LED functions: Figure 13-8 - LED Functions 13.8 XEV20D Technical Specifications Case 4 DIN Connectors Disconnectable Terminal Block 2.5 mm2 for valve outputs and minifit connector for low voltage section Power Supply 24VAC/DC Absorption: 40VA max.
Page 55
Case 4 DIN Kind of Action 1B; Pollution Grade: 2 Software Class: A Rated Inpulsive 2500V; Voltage Overvoltage Category: II Operating -10 to 60°C (14°F to 140°F) Temperature Storage Temperature: -30 to 85°C (-22°F to 185°F) Relative Humidity 20 to 85% (non-condensing) Measuring and PTC probe: -50 to150°C (-58°F Regulation Range...
Page 56
Emerson Climate Technologies Retail Solutions, Inc. and/or its affiliates (collectively “Emerson”), reserves the right to modify the designs or specifications of such products at any time without notice. Emerson does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any product remains solely with the purchaser and end-user.