Replacing components and plant changes
6.1 Failure and replacement of components
Additional information
The following table shows where you can find the step-by-step instructions for replacing
components:
You can find the procedure used to
replace components ...
FF link
Compact FF Link
Note
After every component replacement
Make sure that all systems are free from faults and that the H-system is operating redundantly
and without errors.
6.1.3

Replacement of operator stations in runtime

Replacement of operator stations
When replacing operator stations, a distinction must made between:
● Replacing an OS server
● Replacing an OS client
Note
Information on updating operator stations with redundant OS servers in runtime can be
found in "guidelines on updating a redundant OS in runtime (Page 217)".
Requirements
● The new PC contains the same hardware components.
● An image of the PCs to be replaced is used for the installation.
● The name of the replaced PC is used for the new PC.
● The same IP address is used for the new PC.
● The MAC address is adapted in the project.
192
.... in the following documentation
SIMATIC; Bus Link; FF Link
Operating Instructions
● Replacing the IM 153-2 FF
● Replacing the Field Device Coupler FDC 157
● Restoring the IM 153-2 FF factory settings
SIMATIC; Compact Bus Link; FF Link
Operating Instructions
● Replacing a bus link
● Restoring the Compact FF Link factory settings
High Availability Process Control Systems (V9.0)
Function Manual, 05/2017, A5E39221836-AA