Siemens Simatic PCS 7 Function Manual page 214

High availability process control systems
Hide thumbs Also See for Simatic PCS 7:
Table of Contents

Advertisement

Failure, switchover and reintegration of high availability components
7.7 OS clients
Once OS Server 1 becomes available again, OS Client 1 is switched over to the returning OS
Server 1 because it is the configured preferred server.
Permanent operability is restored after the switchover is complete. OS Client 1 is not available
for the duration of the switchover to OS Server 1. OS Client 2 remains operable without any
interruption.
The status of the "@RM_Master" redundancy tag does not apply to the OS client with preferred
server configuration. The @RM_SERVER_NAME tag indicates the OS server to which this
OS client is currently connected.
Note
Information on updating operator stations with redundant OS servers in runtime can be found
in "guidelines on updating a redundant OS in runtime (Page 217)".
Reaction of an OS client without a preferred server
If no "preferred server" is configured for the OS client in the "Configure Server Data" dialog
box, the OS client connects to the OS server of a redundancy configuration for which the
"@RM_Master" redundancy tag is set.
If the active OS server fails, its redundant OS partner server becomes the master server. You
can recognize which of the two redundant OS servers is currently acting as the master server
by the status of "@RM_Master" redundancy tag. You can trigger a manual switchover by
setting or resetting this tag. All OS clients without a preferred server set connects to the "new"
master server.
Switchover criteria of the OS client
The following faults trigger an OS client switchover. It is not relevant here whether or not a
preferred server has been configured.
● The network connection to the redundant OS server is disrupted.
● The redundant OS server fails, e.g., due to power loss.
● The WinCC project of the redundant OS server is deactivated.
● A disruption of the network connection between OS server and AS, when the option "WinCC
client switch in case of a process connection error" is selected in the "Redundancy" dialog
box.
Additional information
● Online help for
214
WinCC
High Availability Process Control Systems (V9.0)
Function Manual, 05/2017, A5E39221836-AA