Advertisement

Advantages of high availability components
5.4 Distributed I/O
Procedure
1. In the component view, select the SIMATIC H station and double-click the "Hardware"
object in the detail window.
HW Config opens.
2. If the hardware catalog is not visible, select the View > Catalog menu command.
The hardware catalog opens.
3. Double-click on the fieldbus system in the current PCS 7 profile. It depends of required
fieldbus system.
– PROFIBUS DP
– PROFINET IO
4. Double-click the I/O device you want to connect:
– ET 200M
– ET 200iSP
– ET 200SP HA
5. Select the interface module:
– For ET 200M: IM 153-2 in the hardware catalog.
– For ET 200iSP: IM 152-1 whose hardware catalog description is "..., can be used
– For ET 200SP HA: IM 155-6 in the hardware catalog. Depending the type of redundancy
6. Drag the interface module to one of the two fieldbus system lines.
The connection to the redundant line is established automatically.
– If you use PROFIBUS DP:
– If you use PROFINET IO:
134
redundantly in the H system".
you can select the I/O modules shown in the following figure:
Enter the PROFIBUS address in the "Properties - PROFIBUS Interface IM..." dialog box
and click "OK".
Enter the Ethernet address and Subnetmask in the "Properties - PROFINET IO Interface
IM..." dialog box and click "OK".
High Availability Process Control Systems (V9.0)
Function Manual, 05/2017, A5E39221836-AA