Page 1
Water Specialist 2H Control Valve Manual...
Page 2
Page 2 WS2H Control Valve Manual AC Adapter for European Use 1. 220-240 VAC 50Hz input, 24.0 VAC 750mA output. 2. Cable should be one unshielded pair of 22AWG, UV resistant UL2464 compliant wire. 3. Connector details: a. Terminate end with one Molex white housing, P/N 09-50-8043 and four Molex pins, P/N 08-50-0108.
Page 3
WS2H Control Valve Manual Page 3 Separate Source Inlet Relay 2 Output Motor Drive Dry Contacts Functional Relay 1 Output Dry Contacts Optional System Board, Required For Relay Output And Separate Source Inlet Relay outputs 1 & 2 are N.O. SPST dry contacts. Maximum power through relays to be: 3A, 30 VDC 3A, 30 VAC...
Page 4
Page 4 WS2H Control Valve Manual Wiring Diagram Examples, 2 Unit Systems Motor Driven Bypass Manual Over Ride Place in center for normal operation. Two units, no system boards. Display Pod Up forces online, down forces offline Motor Driven Auxilliray (DP) Meter Bypass Switch Input...
WS2H Control Valve Manual Page 5 Wiring Diagrams 3 & 4 unit systems with no optional system boards (4 unit shown) Motor Driven Bypass Manual Over Ride Place in center for normal operation. Up forces online, down forces offline Display Pod Motor Driven Auxilliray (DP) Meter...
Page 6
Page 6 WS2H Control Valve Manual Wiring Diagrams 3 & 4 unit systems with optional system boards for relay outputs and separate source inlet (4 unit shown) Motor Driven Bypass Manual Over Ride Place in center for normal operation. Up forces online, down forces offline Display Pod Separate Motor Driven...
Page 11
WS2H Control Valve Manual Page 11 Typical User Screens USER 1 “REGEN TODAY” will display when a regeneration USER 1 is scheduled, or fl ash for a Displays capacity remaining Does not manually set regeneration. display if volumetric capacity is set to OFF. Capacity remaining can be adjusted in 10 gallon increments by holding the DOWN arrow for >3 seconds.
Page 12 WS2H Control Valve Manual Setting Time of Day SET TIME Accessed by pressing Set Clock while in the User Screens. Use UP and DOWN arrows to scroll hours. AM/PM alternates at midnight. Return to Normal Operation UNIT COUNT ERROR Error and the slave’s unit number will fl...
WS2H Control Valve Manual Page 13 Installer Setup Screens Returns to normal operation after 5 minutes. Accessed by pressing NEXT and UP simultaneously for >3 seconds. INSTALLER 1 INSTALLER 1 Set volumetric capacity or OFF. OFF will not be an option if the day control is set to OFF.
Page 14 WS2H Control Valve Manual System Setup Screens Returns to normal operation after 5 minutes Accessed by pressing NEXT and DOWN simultaneously for >3 seconds. SYSTEM SETUP 1 SYSTEM SETUP 1 Select country. US or SI. This sets the use of a 12 or 24 hour clock and the display of gallons or liters.
Page 15
WS2H Control Valve Manual Page 15 System Setup Screens (continued) SYSTEM SETUP 6 SYSTEM SETUP 6 Select regeneration type. Delayed (dEL-1) Delayed, 2 regenerations per day (dEL-2) Delayed, 3 regenerations per day (dEL-3) Delayed, 4 regenerations per day (dEL-4) On 0 Delayed with multiple regenerations allowed per day would be used either to reduce the reserve volume, or to accommodate a small system relative to the treatment demand.
Page 16 WS2H Control Valve Manual Timer Screens Returns to normal operation after 5 minutes. Accessed by pressing NEXT and DOWN simultaneously for >3 seconds, then by pressing NEXT and DOWN simultaneously again for >3 seconds. TIMER 1-A TIMER 1-A Cycle Units Range...
Page 17
WS2H Control Valve Manual Page 17 Timer Screens (continued) TIMER 2 TIMER 2 TIMER 2 Set output 1. These settings will only be allowed with the system board installed. Time: Relay is turned on after specifi ed time from the start of regen and is left on for a specifi ed time. Cycle: Relay is turned on after the start of a specifi...
Page 18 WS2H Control Valve Manual Cycle Setup Screens Returns to normal operation after 5 minutes. Accessed by pressing NEXT and DOWN simultaneously for >3 seconds, then by pressing NEXT and DOWN simultaneously again for >3 seconds, then by pressing NEXT and DOWN simultaneously for >3 seconds a third time. CYCLE SETUP 1-A CYCLE SETUP 1-A Select fi...
Page 19
WS2H Control Valve Manual Page 19 Cycle Setup Screens (continued) CYCLE SETUP 2 CYCLE SETUP 2 Select regeneration repeats, 1-10 or OFF. Repeats regeneration cycle sequence 1 a selected number of times before regenerating a single time with sequence 2. The following screens only show if the unit is programmed for multiple regenerations in the previous screen.
Page 20 WS2H Control Valve Manual Diagnostic Screens Returns to normal operation after 5 minutes. Accessed by pressing UP and DOWN simultaneously for >3 seconds. All Diagnostic History screens are resettable with the History Reset sequence while in the Diagnostics1 screen. Holding the Set Clock and Regen buttons for >...
Page 21
WS2H Control Valve Manual Page 21 Diagnostic Screens (continued) DIAGNOSTIC 5 Max fl ow rate of the day DIAGNOSTICS 5 Maximum fl ow rate for the last 28 days. Automatically Toggles Simultaneously press UP and DOWN. DIAGNOSTICS 5-B DIAGNOSTIC 5-B Max fl...
Page 22 WS2H Control Valve Manual Valve History Returns to normal operation after 5 minutes. Non-Resettable Accessed by pressing UP and DOWN simultaneously for >3 seconds, then by pressing UP and DOWN simultaneously again for >3 seconds. HISTORY 1 HISTORY 1 Total days since startup.
Page 23
WS2H Control Valve Manual Page 23 Treated Water Supply Raw Water Inlet Service To Drain Hard Water Supply Raw Water Inlet Backwash...
Page 24
Page 24 WS2H Control Valve Manual To Drain Hard Water Solution Is Supply Drawn In Raw Water Inlet Draw To Drain Hard Water Supply Raw Water Inlet Slow Rinse...
Page 25
WS2H Control Valve Manual Page 25 To Drain Hard Water Supply Raw Water Inlet Rinse Treated Water Supply Treated Water To Tank Raw Water Inlet Softwater Fill...
Page 26
Page 26 WS2H Control Valve Manual Front Cover and Drive Assembly Drawing No. Order No. Description Quantity V3068 WS2 POD ASY V3241-01 WS2 PC BOARD DISPLAY V3248 WS2 CABLE DISPLAY POD V3242-01 WS2 PC BOARD VALVE V3224-01R WS2 COVER ASY PLATINUM V3107-01 WS1 MOTOR ASY V3226-01...
Page 27
Not Shown D1300-01 TOP BAFFLE DFSR CLACK 2/63MM **V3054 WS2 4 IN BASE CLAMP ASY includes a V3276 WS2 BOLT HEX SS 5/16-18X1-3/4 and V3269 WS2 NUT 5/16-18 SS HEX. In 2007, a u-shaped retaining clip (V3501) was added to commercial meter assemblies to hold the turbine assembly in place. If V3501 is present, service or replace the turbine by: 1.
Page 28
Page 28 WS2H Control Valve Manual Brine Valve Body and Injector Components Drawing No. Order No. Description Quantity V3237-01 WS2 SOFTFILL TUBE ASY V3236-01 WS2 INJECTOR TUBE ASY V3289 O-RING 344 V3067 WS2 BRINE BODY ASY V3477 WS2 INJECTOR CAP V3152 O-RING 135 V3275...
Page 29
WS2H Control Valve Manual Page 29 V3064 WS2H/2L 4 INCH BASE ASY Drawing No. Order No. Description Quantity V3202-01 WS2 BASE V3281 O-RING 348 V3055 WS2H/2L FLANGE BASE ASY Drawing No. Order No. Description Quantity V3444 WS2 SCREW HEXCAP 5/16-18X2.5SS V3293 WS2 WASHER SS 5/16 FLAT V3445...
WS2H Control Valve Manual Page 33 Error Codes Error Description Possible Cause Drive motor is not engaged with mating gear Faulty drive motor or wiring Encoder on main board is 1001 Reflectors on reduction gear are dirty or damaged not registering pulses Circuit board is not properly engaged with drive bracket Faulty encoder / main board Debris jamming piston...
Page 34
Page 34 WS2H Control Valve Manual Order No. V3010-2B Order No. V3010-2A US Units US Units Total Total Slow Rinse Slow Rinse Draw Draw Pressure (psi) Pressure (psi) Order No. V3010-2D Order No. V3010-2C US Units US Units Total Total Slow Rinse Slow Rinse Draw...
Page 35
WS2H Control Valve Manual Page 35 Order No. V3010-2A Order No. V3010-2B Metric Units Metric Units Total Total Slow Rinse Slow Rinse Draw Draw Pressure (kPa) Pressure (kPa) Order No. V3010-2C Order No. V3010-2D Metric Units Metric Units Total Total Slow Rinse Slow Rinse Draw...
Page 36 WS2H Control Valve Manual Revision History: 06/21/07 PAGE 3: 2) Maximum power through relays a. 1A, 30 VDC b. 1A, 30 VAC PAGE 29: V3260BSPT-02 WS2 SIDE MOUNT BASE BSPT ASY Added drawing and table PAGE 31: 6 V3264 WS2 BYPASS REDUCTION GEAR AXLE 3 N/A 06/25/07 PAGE 29: V3260-02 WS2 SIDE MOUNT BASE NPT...