Operation of the Unit
CP. 8
DC - output voltage /
peak value
CP. 9
Heat sink temperature
CP.10
Charging time factor
CP.11
Analog output 1 gain
CP.12
Analog output 2 gain
CP.13
AC-Phase current L1
CP.14
AC-Phase current L2
CP.15
AC current L3
GB - 20
This display enables a detection of short-term voltage peaks, as the highest
value that occurred is stored.
The peak value can be reset with UP or Down when the unit is switched on.
Switching off the unit deletes the peak value.
Display of the actual heat sink temperature in °C. First a prewarning is given
out if the heat sink temperature is too high, so a controlled deceleration of
the unit is possible. The thyristors are blocked when reaching the max. heat
sink temperature of 90 °C, if there is no reaction to the pre-warning.
The charge time is dependent on the connected total capacity. The preset
value of 100% is 16 s. If the charge time should be exceeded in case of
very large capacities, the charge time can be extended up to 500 % with the
charge time factor.
At a gain of "1" the analog output 1 outputs a signal in a range of 0...10 VDC
= 0...150 % I
which corresponds to the DC-output current. The gain can
DC
be adjusted with CP.11 in a range of ±20,00. The analog output can be
adapted thereby to individual requirements.
At a gain of "1,00" the analog output 2 outputs a signal in a range of
0...10 VDC = 0...800 V U
The gain can be adjusted with CP.11 in a range of ±20,00. The analog
output can be adapted thereby to individual requirements.
CP.13 displays the rms value of the input current of phase L1 in ampere.
CP.14 displays the rms value of the input current of phase L2 in ampere.
CP.15 displays the rms value of the input current of phase L3 in ampere.
which corresponds to the DC- output current.
DC