(First) Commissioning
• "New System" (if you would like to start the
system or perform changes to the system
configuration)
The following parameters must be set when "New System" is selected:
(default setting shown in bold)
Country configuration: 003#01 Country (GER/VDE0126-1-1, GR_PCC, GR_INSULAR)
Date : 003#02 Dt (dd.mm.yyyy)
Time: 003#03 Tm (hh:mm:ss)
Battery type: 003#04 BatTyp (VRLA, FLA, NiCd)
Battery capacity: 003#05 BatCpyNom (50 Ah to 10,000 Ah, 140 Ah)
Nominal grid current: 003#06 GdCurNom (0 A to 25 A, 16A)
• "New Battery" (if you would like to change the
main battery settings, but retain the system
configuration)
"New Battery"
The "New Battery" option is required whenever you want to install a new battery in the
backup system.
With this option, only specific battery settings can be reset and adjusted. System settings
are not affected.
The following parameters must be set when "New Battery" is selected:
(default setting shown in bold)
Battery type: 003#04 BatTyp (VRLA, FLA, NiCd)
Battery capacity: 003#05 BatCpyNom (50 Ah to 3,000 Ah, 140 Ah)
8. The following message appears after the button
has been turned again.
88
SBU2200-TEN083320
SMA Solar Technology AG
Technical Description