SMA S Technical Description page 144

Backup-system
Table of Contents

Advertisement

Parameter Lists
Menu
Parame
Parameter name
no.
ter no.
222
10
ChrgVtgFlo
222
11
BatTmpCps
222
12
AutoEquChrgEna
223# Bat Protection
223
01
BatPro1TmStr
223
02
BatPro1TmStp
223
03
BatPro2TmStr
223
04
BatPro2TmStp
223
05
BatPro1Soc
223
06
BatPro2Soc
223
07
BatPro3Soc
224# Bat Silentmode
224
01
SilentEna
224
02
SilentTmFlo
(Stby)
224
03
SilentTmMax
(Stby)
230# Set Backup
Menu
Parame
Parameter name
no.
ter no.
231# General
231
01
AcSrcFrqDel
144
SBU2200-TEN083320
Range/unit
Default
value
V
2.25
mV/degC
4.0
Disable
Enable
Enable
hhmmss
220000
hhmmss
060000
hhmmss
170000
hhmmss
090000
%
20
%
15
%
10
Disable
Disable
Enable
h
3
h
12
Range/unit
Default
value
Hz
4,8
SMA Solar Technology AG
Description
cell voltage nominal value for float charge
2.25 = VRLA
2.25 = FLA
1.55 = NiCd
depending on the setting in QCG
battery temperature compensation
4.0 = VRLA
4.0 = FLA
0.0 = NiCd
depending on the setting in QCG
activates automatic equalization charge
time for starting battery preservation
mode level 1
time for stopping battery preservation
mode level 1
time for starting battery preservation
mode level 2
time for stopping battery preservation
mode level 2
SOC limit for preservation mode level
1
SOC limit for preservation mode level
2
SOC limit for preservation mode level
3
allows silent mode on the grid
max. time for float charge until transfer into
silent
max. time for silent mode until transfer into
float
Description
frequency increase for disconnecting AC
feed-in generators
Technical Description