Parame
Parameter name
no.
ter no.
231
02
PvFeedTmStr
231
03
PvFeedTmStp
231
04
ExtLkTm
231
09
ExtSrc
232# Grid Control
232
01
GdVtgMin *
232
02
GdVtgMax *
232
03
GdCurNom
232
04
GdFrqNom
232
05
GdFrqMin *
232
06
GdFrqMax *
232
07
GdVldTm
232
08
GdMod *
232
09
GdRvPwr *
232
10
GdRvTm *
232
15
GdAISns *
232
37
GdVtgIncProEna *
232
38
GdVtgIncPro
232
40
Country;---,;0;I;I;Country *
Parameters marked with *
Parameters designated with * are safety-related grid monitoring parameters. To change
the SMA grid guard parameters, you must enter your personal SMA grid guard password
(installer code). Call the SMA Hotline to obtain your personal SMA grid guard password.
Technical Description
Range/unit
Default
value
hhmmss
040000
hhmmss
220000
min
20
Grid
Grid
V
189
V
259,5
A
16
Hz
50
Hz
47,65
Hz
50,15
sec
30
GridCharge
GridCharge
GridFeed
W
100
sec
5
Normal
Low
Medium
Normal
High
Disable
Enable
Enable
V
253
Adjusted
GER_VDE012
6-1-1
Other
GER_VDE012
6_1_1;
GR_PPC;
GR_INSULAR
Parameter Lists
Description
start time for PV grid feeding
stop time for PV grid feeding
lock time after reverse power or relay
protection
grid operation
minimum grid voltage
maximum grid voltage
nominal grid current
nominal grid frequency
minimum grid frequency
maximum grid frequency
minimum time required for grid (voltage
and frequency) to be within permissible
range for connection
grid interface
permissible grid reverse power (effective
power)
permissible time for grid reverse power
AI sensitivity
allows voltage rise protection
threshold for voltage rise protection
country selection