Parame
Parameter name
no.
ter no.
221
04
BatTmpMax
221
05
BatTmpStr
222# Bat Chargemode
222
01
BatChrgCurMax
222
02
AptTmBoost
222
03
AptTmFul
222
04
AptTmEqu
222
05
CycTmFul
222
06
CycTmEqu
222
07
ChrgVtgBoost
222
08
ChrgVtgFul
222
09
ChrgVtgEqu
Technical Description
Range/unit
Default
value
degC
40
degC
35
A
80
min
120
h
5
h
10
d
14
d
180
V
2.4
V
2.4
V
2.4
Description
maximum battery temperature
battery restart temperature following stop
due to overtemperature
battery charging current limit (depends on
nominal battery capacity), 60 % of the
nominal battery capacity (221#02)
absorption time for normal charge
120 = VRLA
90 = FLA
300 = NiCd
depending on the setting in QCG
absorption time for full charge
5 = VRLA
5 = FLA
7 = NiCd
depending on the setting in QCG
absorption time for equalization charge
10 = VRLA
10 = FLA
10 = NiCd
depending on the setting in QCG
full charge cycle time
equalization charge cycle time
cell voltage nominal value for normal
charge
2.4 = VRLA
2.55 = FLA
1.65 = NiCd
depending on the setting in QCG
cell voltage nominal value for full charge
2.4 = VRLA
2.5 = FLA
1.65 = NiCd
depending on the setting in QCG
cell voltage nominal value for equalization
charge
2.4 = VRLA
2.5 = FLA
1.65 = NiCd
depending on the setting in QCG
SBU2200-TEN083320