SMA S Technical Description page 156

Backup-system
Table of Contents

Advertisement

Troubleshooting/Problem Solving
Displ.
Level
Description
no.
F145
3
overtemperature (voltage converter)
Category BAT
F206
3
battery overtemperature
F208
3
battery overvoltage (internal limit for cell voltage)
W210
1
battery overvoltage warning (depending on charging voltage nominal value)
W211
1
insufficient battery temperature warning
W212
1
high battery temperature warning
Category EXT
W309
1
relay protection
W315
1
grid disconnection, external voltage too low
W319
1
grid disconnection, external voltage too high
W323
1
grid disconnection, external frequency too low
W327
1
grid disconnection, external frequency too high
W331
1
grid disconnection due to anti-islanding (unwanted stand-alone grid)
W335
1
grid disconnection due to breached voltage limits
W339
1
grid disconnection due to voltage rise protection
W360
1
grid disconnection due to overcurrent
Category RLY
F605
4
transfer relay does not open
Category SYS
W702
1
internal restart
F703
3
timeout during internal processing
F705
4
DSP watchdog has been triggered
F706
4
watchdog meter has expired (watchdog triggered several times in succession)
F710
4
autostart meter has expired (several autostarts in succession)
F711
2
DSP hardware error
F712
2
internal electronics monitoring (HTSS error)
W713
1
watchdog has been triggered
F714
2
internal overvoltage
F722
3
short circuit in battery temperature sensor
F723
3
cable break on battery temperature sensor
W738
1
synchronization not successful
F739
3
internal device communication BFR-DSP missing
156
SBU2200-TEN083320
SMA Solar Technology AG
Technical Description

Advertisement

Table of Contents
loading

This manual is also suitable for:

Src-1As-box-s.1Sbu 2200

Table of Contents