Spare Parts and Service

Plate Heat Exchanger Inspection
Check the plate heat exchanger for fouling.
Check the functionality of the condensate drainage.
 Check the bypass and mixing damper flaps for free
rotation.
 Check the damper flaps for full closing
Gas Heater Block Check
The gas heater inspection must be carried out once a year,
including burner adjustment and flue gas measurement!
Verification Measurements
After completing the regular inspection of the air-handling
unit, it is necessary to verify and record its actual perfor-
mance parameters.
Overall check
Clean all parts of the air-handling unit:
Min. 1x per year or more frequently, if needed
(recommended cleaning solution – 10 parts of a dish
washing cleaner, 45 parts of Isopropanol, 45 parts of
water – pH 5–9, do not use cleaners containing active
chlorine). Max. 50°C when steam cleaning equipment
is used.
When high-pressure cleaning equipment is used, there
is a risk of paint damage, especially in the elbows
Don't use brushes or similar abrasive tools and
cleaners
First, probe on a little surface area
Use the same technique on the entire surface area to
prevent differences in colour in some areas
20
Air Handling Units
Spare Parts and Service
Spare parts are not included in the air-handling unit deli-
very. If any spare parts are needed, they can be ordered
from REMAK a.s. or the regional distributor. In your order,
specify the unit serial or purchase order number, and the
parts needed.
Spare Filter Inserts
A complete set of filter inserts can be ordered. Specificati-
on of the filter type (bag, compact, insert, or grease/metal
filter), XP air-handling unit size and filtration class will do.
There is no need to specify the types of individual filter in-
serts of the filter.
Active Carbon Cartridges
The active carbon cartridges are designed for a specific
composition of filtered gases. The carbon cartridge is re-
activated as a whole. Active carbon which contains toxic
substances, radioactive impurities or PCB cannot be re-
activated!
Service
Guarantee and regular servicing can be ordered from
REMAK a.s. or the regional distributor.
The manufacturer can authorize trained service providers
to perform this service; their list can be found at
www.remak.eu
Disposal and Recycling
When using or disposing of the air-handling unit, it is ne-
cessary to observe the respective national environmental
protection and waste disposal regulations. In case of final
unit liquidation, it is necessary to follow the policy of sorted
waste disposal; this means to respect differences in mate-
rials and their composition.
It is necessary to hire a provider specialized in sorted was-
te disposal in accordance with applicable local standards
and regulations.
Active carbon which contains toxic substances, radioactive
impurities or PCB must be disposed of in accordance with
applicable legal regulations.
After exceeding its service life limit, the unit belongs to
waste group Q14 according to the Waste Act (č.185/2001
Sb.).
Waste Classification
(in accordance with Directive No. 381/2001 Sb.)
15 01 01 cardboard box
(paper and cardboard packaging)
15 01 02 polyester packaging pads
(plastic packaging).
15 01 03 pallet
(wooden packaging)
Disabled device and its parts:
16 02 06 metal and aluminium parts
insulating material
(other items from disabled devices)
15 02 03 filtering materials
16 02 15 electrical parts
(dangerous items from disabled devices)