Connection of Heat Exchangers
Water Connected Air-handling Component
Installation
Recommendations on water quality for heat exchangers
that operate using low pressure hot water (LPHW) and
chilled water:
A good water quality – e.g. salt and lime-free drinking
water – increases the
lifetime and efficiency of the heat exchanger.
Check the limiting values shown in the table annually to
prevent damage to
the hydraulic system and its components.
If necessary inhibitors must be added.
Note:
These limiting values are only basic information about the
water quality and do not form any basis for a guarantee!
Description
Symbol
Hydrogen ion
pH
concentration
Hard-
Calcium and
ness
magnesium content
(Ca/Mg)
Chloride ions
Cl-
Carbon dioxide
Fe
3+
Iron ions
Mg
2+
Carbon dioxide
CO
2
Hydrogen sulphate
H
S
2
Oxygen
O
2
Chlorine
Cl
2
Ammonia
NH
3
Ratio of carbons/
HCO
sulphates
SO
2-
4
1/1,78 °D = 1 °Fr, with 1°Fr = 10 g CaCO
ppm = parts per million (mg/l)
ppm = parts per billion (µg/l)
10
Effects in vent
Values
of deviation
< 7
Corrosion
7,5 - 9
> 9
Fouling
4 – 8,5 °D
> 8,5
Fouling
< 50 ppm
Corrosion
< 0,5 ppm
Corrosion
< 0,05
Corrosion
ppm
< 10 ppm
Corrosion
< 50 ppb
Corrosion
< 0,1 ppm
Corrosion
< 0,5 ppm
Corrosion
< 0,5 ppm
Corrosion
/
2-
>1
<1
Corrosion
3
/m
3
3