Kospel EKCO.LN2M Assembly And Operating Manual

Kospel EKCO.LN2M Assembly And Operating Manual

Electric central heating flow boiler

Advertisement

Electric Central Heating Flow Boiler
EKCO.LN2M
EKCO.L2M
Assembly and operating manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EKCO.LN2M and is the answer not in the manual?

Questions and answers

Kristina
May 30, 2025

How to set up EKCO.LN2M-25kw to work on 12kw

1 comments:
Mr. Anderson
May 30, 2025

To configure the Kospel EKCO.LN2M-25kW for 12 kW operation, you must limit the boiler’s output power. The EKCO.LN2M model supports multiple power settings, including 12 kW. This can be done by selecting the desired rated power during installation or setup.

Ensure the following:

1. Power Supply: Use a 400V 3N~ power supply.
2. Rated Current: At 12 kW, rated current is 3x17.3 A.
3. Power Cable:
- Minimum cross-section: 5 x 2.5 mm².
- Maximum cross-section: 5 x 25 mm².
4. Maximum Network Impedance: 0.27 Ω.

Adjust the boiler settings or internal configuration (e.g., DIP switches or software settings) to limit the power to 12 kW. This should be done by qualified personnel according to the manufacturer's instructions.

This answer is automatically generated