JUMO dTRANS T07 Manual

JUMO dTRANS T07 Manual

Two-channel temperature transmitter with hart/ex/sil for installation into terminal head form b and for installation on din rail
Hide thumbs Also See for dTRANS T07:

Advertisement

Quick Links

JUMO dTRANS T07
Two-channel temperature transmitter with HART/Ex/SIL
for installation into terminal head form B and for installation on DIN rail
Brief description
The JUMO dTRANS T07 device series is a two-channel temperature transmitter with HART
communication. The devices are available in 2 versions: for installation in a B-head or for DIN-
rail mounting. The variants with Ex and SIL approval (IEC 61508) for SIL 2/3 (hardware/software)
enable secure use in demanding process applications.
The configurable transmitters transmit converted signals from RTD temperature probes and ther-
mocouples (TC) as well as from resistor and voltage sensors to the galvanically isolated
4 to 20 mA current output. Internal sensor monitoring functions and device error detection en-
able a high degree of measuring point availability.
The optional plug-on display BD7 can be used to display the current measured value on the B-
head variant.
The JUMO dTRANS T07 device series is tailor-made for all industries like chemicals, oil, gas,
and power plants & energy, as well all others in which safe and reliable temperature measure-
ments are required.
1
HART® is a registered trademark of the FieldComm Group™
Block diagram
Input signals
RTD
Temperature probe
TC
Thermocouple
Resistor/Potentiometer
+
Voltage sensor
-
Voltage supply
Version for B-head:
DC 11 to 42 V
Version for DIN rail:
DC 12 to 42 V
Approvals/approval marks (see "Technical data")
V4.00/EN/00681575
Output signal
4 to 20 mA
Communication
HART communication
for configuration and diagnosis
(HART 7 protocol)
Data Sheet 707080
1
Type 707080 (dTRANS T07 B)
Type 707082 (dTRANS T07 T)
Special features
Two universal measurement inputs
(RTD, TC, Ω, mV)
High degree of accuracy
(0.1 K with Pt100 sensor)
Output 4 to 20 mA
(single channel, loop powered)
Two enclosure versions
(B-head or DIN rail)
HART 7 protocol
with extension for "secure HART"
SIL 2/3 hardware/software
according to IEC 61508
Reliable measurement operation
through sensor monitoring and
device hardware error detection
Optional plug-on display BD7
for B-head device version
70708000T10Z001K000
Page 1/28

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the dTRANS T07 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for JUMO dTRANS T07

  • Page 1 The optional plug-on display BD7 can be used to display the current measured value on the B- head variant. The JUMO dTRANS T07 device series is tailor-made for all industries like chemicals, oil, gas, and power plants & energy, as well all others in which safe and reliable temperature measure- ments are required.
  • Page 2: Type Overview

    Operating mode The temperature transmitters in the dTRANS T07 series are two-wire transmitters with two measurement inputs and one analog output. The devices transmit both converted signals from RTD temperature probes and thermocouples, but also resistance and voltage signals via the HART communication and as a 4 to 20 mA current signal.
  • Page 3 Temperature-dependent switching between sensors that are used in different measuring ranges. • Average value measurement or differential measurement from two sensors. • Average value measurement with sensor redundancy Not all modes are available for SIL operation SIL safety manual for dTRANS T07 series (SIL designs). V4.00/EN/00681575 70708000T10Z001K000...
  • Page 4: Technical Data

    Data Sheet 707080 Page 4/28 Technical data Analog input General information Measurand Temperature (temperature-linear transmission behavior), resistance and voltage. Measuring range It is possible to connect two mutually independent sensors. The measurement inputs are not galvanically isolated from each other. With a 2-channel measurement, the same measurement unit must be configured on both channels (e.g.
  • Page 5 Data Sheet 707080 Page 5/28 Thermocouples (TC) Standard Designation Measuring range limits Minimum measuring Possible temperature range Recommended tempera- span ture range Type A (W5Re-W20Re) (30) 0 to +2500 °C 0 to +2500 °C 50 K Type B (PtRh30-PtRh6) (31) +40 to +1820 °C +500 to +1820 °C 50 K...
  • Page 6 ≤ 3.8 mA during the switch-on delay Not possible in SIL mode; refer to the safety manual for the JUMO dTRANS T07 series (SIL versions). Does not apply to SIL mode; refer to the safety manual for the JUMO dTRANS T07 series (SIL versions). V4.00/EN/00681575...
  • Page 7 Data Sheet 707080 Page 7/28 Features Physical input measuring range of the sensors Cu50, Cu100, RTD polynomial, Pt50, Pt100, Ni100, Ni120 10 to 400 Ω Pt200, Pt500, Pt1000 10 to 2000 Ω Thermocouple types: A, B, C, D, E, J, K, L, N, R, S, T, U -20 to 100 mV Response time The update of the measured value depends on the sensor type and the circuit type, and is in the following ranges:...
  • Page 8 Data Sheet 707080 Page 8/28 Maximum measurement deviation for RTD temperature probes Measurement deviation (±) Standard Designation Measuring range Digital Maximum Related to the measured value Pt100 (1) -200 to +850 °C ≤ 0.12 °C 0.06 °C + 0.006 % × (MV - MRS) Pt200 (2) -200 to +850 °C ≤...
  • Page 9 Data Sheet 707080 Page 9/28 Maximum measurement deviation for thermocouples (TC) Measurement deviation (±) Standard Designation Measuring range Digital Maximum Related to the measured value Type A (30) 0 to +2500 °C ≤ 1.33 °C 0.80 °C + 0.021 % × (MV - MRS) IEC 60584-1 Type B (31) +500 to +1820 °C...
  • Page 10 + influence of voltage supply digital + influence of voltage supply D/A The specifications for the measurement deviation correspond to 2 σ (Gaussian normal distribution). Different measurement deviations apply in SIL mode SIL safety manual for dTRANS T07 series (SIL designs). V4.00/EN/00681575 70708000T10Z001K000...
  • Page 11: Operating Influences

    Data Sheet 707080 Page 11/28 Operating influences The specifications for the measurement deviation correspond to 2 σ (Gaussian normal distribution). Operating influences 'ambient temperature' and 'voltage supply' for RTD temperature probes Standard Designation Ambient temperature: Voltage supply: Effect (±) per 1 °C change Effect (±) per 1 V change Digital Digital...
  • Page 12 Data Sheet 707080 Page 12/28 MV = measured value; MRS = measuring range start of the relevant sensor. Operating influences 'ambient temperature' and 'voltage supply' for thermocouples (TC) Standard Designation Ambient temperature: Voltage supply: Effect (±) per 1 °C change Effect (±) per 1 V change Digital Digital...
  • Page 13: Long-Term Drift

    Data Sheet 707080 Page 13/28 Long-term drift Long-term drift of RTD temperature probe Standard Designation Long-term drift (±) After 1 year After 3 years After 5 years Related to the measured value ≤ 0.016 % × (VM - DEM) or ≤...
  • Page 14 Data Sheet 707080 Page 14/28 Standard Designation Long-term drift (±) After 1 year After 3 years After 5 years Related to the measured value ≤ 0.024 % × (MV - MRS) or ≤ 0.037 % × (MV - MRS) or ≤...
  • Page 15: Sensor Calibration

    Data Sheet 707080 Page 15/28 Sensor calibration Sensor RTD sensors are among the most linear of all temperature measuring elements. Nonetheless, it is still necessary to lin- transmitter earize the output. For significant improvement of the temperature measurement accuracy, the device enables the use of matching two methods: •...
  • Page 16: Voltage Supply

    Data Sheet 707080 Page 16/28 Voltage supply Devices without Ex-approval Voltage supply (protected against polarity reversal) Head transmitter DC 11 V ≤ V ≤ 42 V (standard) DC 11 V ≤ V ≤ 32 V (SIL operation) DIN rail device DC 12 V ≤...
  • Page 17: Environmental Influences

    Data Sheet 707080 Page 17/28 Environmental influences Ambient temperature for all devices without Ex-approval Standard operation -40 to +85 °C SIL operation -40 to +70 °C Ambient temperature for head transmitters with Ex-approval (without display) Temperature class Ambient temperature zone 1 Ambient temperature zone 0 -40 to +58 °C -40 to +46 °C...
  • Page 18: Approvals/Approval Marks

    Data Sheet 707080 Page 18/28 Case All materials used are RoHS compliant. Versions for Versions for B-head mounting DIN-rail mounting Material of enclosure body Polycarbonate (PC), corresponds to UL94, V-2 UL recognized Material of connection terminals Nickel-plated brass with gold-plated contacts Potting material WEVO PU 403 FP / FL Terminal design...
  • Page 19: Operation On The Device

    If the LED lights up green, this signals that the voltage supply is OK. Status LED Off: No diagnostic message Illuminated red: Category F diagnostic message dTRANS T07 Flashing red: Category C, S or M diagnostic mes- sage Internal service interface Not intended for use V4.00/EN/00681575...
  • Page 20: Remote Control Configuration

    Remote control/configuration The devices are configured via the HART® communication. To do this, either a field communicator with a device-specific JUMO DD (Device De- scription) file can be used, or a PC/laptop with installed PACTWare™ user interface and JUMO DTM (Device Type Manager) driver.
  • Page 21 Mounting elements for plug-on display BD7 internal service interface (not intended for use) DIN rail device dTRANS T07 17.5 114.9 Terminal head for dTRANS T07 AB 7 with display window in the cap Specifications Cable inlets Ambient temperature -50 to +150 °C without cable fitting 107.5...
  • Page 22 Data Sheet 707080 Page 22/28 Field enclosure for dTRANS T07 FG 7 with display window in the cap Specifications Cable inlets 107.5 Ambient temperature -50 to +150 °C without cable fitting Material Enclosure Aluminum, polyester powder coating Seals Silicone Cable inlet screw connections M20 ×...
  • Page 23: Connection Diagram

    Connection examples Types without Ex-approval (707080 to 707083) Controller Indicating Recorder device JUMO Power supply unit dTRANS T07 for transmitter 4 to 20 mA Types with Ex-approval (707085 to 707088) Ex-area area Controller Indicating Recorder...
  • Page 24 Data Sheet 707080 Page 24/28 Terminal assignment for the head transmitter For the connection, it is possible to use both rigid and flexible wires with a conductor cross section ≤ 2.5 mm From a sensor wire length of 30 m a shielded wire must be used. The use of shielded wires is generally recommended. Connection for Explanations Terminals...
  • Page 25 Data Sheet 707080 Page 25/28 Connection for Explanations Terminals Analog input (sensor input) 2 RTD temperature probe ▪ Sensor current ≤ 0.3 mA ▪ Compensation for the line resistance is possible (0 to 30 Ω) 2-wire circuit RTD temperature probe ▪...
  • Page 26 Data Sheet 707080 Page 26/28 Terminal assignment for DIN rail devices For the connection, it is possible to use both rigid and flexible wires with a conductor cross section ≤ 2.5 mm From a sensor wire length of 30 m a shielded wire must be used. The use of shielded wires is generally recommended. Connection for Explanations Terminals...
  • Page 27 Data Sheet 707080 Page 27/28 Connection for Explanations Terminals Resistance/potentiometer ▪ Sensor current ≤ 0.3 mA ▪ Sensor line resistance max. 50 Ω per line 3-wire circuit Resistance/potentiometer ▪ Sensor current ≤ 0.3 mA ▪ Sensor line resistance max. 50 Ω per line 4-wire circuit Thermocouple Voltage sensor...
  • Page 28: Order Details

    T07 B Ex – Two-wire transmitter with Ex approval for installation in termi- nal head, form B 707086 dTRANS T07 B Ex SIL – Two-wire transmitter with Ex and SIL approval for installa- tion in terminal head, form B 707087 dTRANS T07 T Ex –...