Troubleshooting / Quick Reference Guide
Active Alarm
LED
OVERVOLTAGE
RED
AUXILIARY
RED
SHUTDOWN
LOW BATTERY
YELLOW
BATTERY
YELLOW
PROBLEM
CHARGER
YELLOW
WARNING
CHARGER
YELLOW
MISSING AC
SERVICE A
YELLOW
SERVICE B
YELLOW
INSPECT
YELLOW
BATTERY
38
Problem
Things to Check
Unit will not start in
Check the LEDs /
AUTO with utility loss.
screen for alarms.
Check auxiliary
Unit will not start.
shutdown switches
Yellow LED illuminated
Check the screen for
in any state.
additional information.
Yellow LED illuminated
Check the screen for
in any state.
additional information.
Yellow LED illuminated
Check the screen for
in any state.
additional information.
Yellow LED illuminated
Check the screen for
in any state.
additional information.
Yellow LED illuminated
Check the screen for
in any state.
additional information.
Yellow LED illuminated
Check the screen for
in any state.
additional information.
Yellow LED illuminated
Check the screen for
in any state.
additional information.
Solution
Contact an IASD.
Set auxiliary shutdown switch(es) to
CLOSED (I). Clear alarm.
Clear alarm. Using the control panel,
check the battery by navigating to the
BATTERY MENU option from the MAIN
MENU. If battery condition displays
GOOD, contact an IASD. If control panel
displays CHECK BATTERY, replace the
battery.
Contact an IASD.
Contact an IASD.
Contact an IASD.
Perform SERVICE A maintenance. Press
ENTER to clear.
Perform SERVICE B maintenance. Press
ENTER to clear.
Inspect battery. Press ENTER to clear.
Owner's Manual for 60 Hz Air-Cooled Generators