All output monitors on the Thermolator can be enabled or dis-
abled permanently through the OM Enable/Disable Menu in
Test Mode.
You need to use this feature if you have replaced the mother-
board, or if dip switches 7 and 8 have been changed erro-
neously. This will enable any required output monitors that
were disabled and give fuse failures.
1
Enable Test Mode.
2
Press any key to display the first test menus.
3
Select the OM Enable/Disable menu.
Press and hold the Setpoint
to each test menu until the controller indicates "oS1" in
the actual display and the status of the selected output in
the Select display.
Press the Setpoint L L or M M key to change the
4
status.
Each press of the key changes the output status
from ON to OFF or OFF to ON.
O
UTPUT
MODEL TYPE
OM1 Pump
OM2 Heat
OM3 Cool
OM4 Vent
OM5 Purge (TW-2 option only)
5
Press the Setpoint
Repeat Step 4 to change the status of the output, or press
any key to continue indexing through the outputs.
Save changes and exit the output menu.
6
Press and hold the Select
changes and exit.
UGH015/0100
key for 3 seconds to index
M
S
ONITOR
ELECTION
DI
ON
ON
ON
OFF
ON
to select the next output.
key for 3 seconds to save the
Thermolator TW-1 and TW-2
G
UIDE
CC
IC (TCC)
ON
ON
ON
ON
ON
ON
ON
OFF
ON
OFF
D
ISABLING OR
E
NABLING
O
UTPUT
M
ONITORS
M
AINTENANCE
5-9

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vtr1-diVtr2-di

Table of Contents