Output Test - Conair Thermolater vacuTrac User Manual

Positive/negative pressure water temperature controller with tw-1 or tw-2 microprocessor
Table of Contents

Advertisement

O
T
UTPUT
EST
5-8
M
AINTENANCE
The Output Test verifies the function of outputs available on
the various TW-1 and TW-2 models. Not all outputs are used
on all models. The performance evaluation of the inputs is
based on the output monitors (OM).
1
Connect all outputs to the system.
IMPORTANT: Testing each output requires the fir-
ing of the associated solid state relay. Make sure an
output device is connected to the controller, other-
wise the test result will be erroneous.
2
Enable Test Mode.
3
Press any key to display the first test menus.
4
Select the Output Test menu.
Press and hold the Setpoint
to each test menu until the controller displays "oUt".
Repeatedly press and release any key to test.
5
With each key press and release, the left display will indi-
cate the number of the output being tested (oS1= OM1;
oS2 = OM2; etc.). The right display indicates either "1"
for a good output or "O" for a failed output.
Only outputs that are actually used by the particular model
will be tested.
6
Exit the test and enter the next test.
Press and hold the Setpoint
and index to the next test.
Thermolator TW-1 and TW-2
key for 3 seconds to index
key for 3 seconds to exit
UGH015/0100