Lamtec LT 2 Assembly And Commissioning Manual page 89

Simultaneous measurement of oxygen and oxidizing components
Hide thumbs Also See for LT 2:
Table of Contents

Advertisement

10 Appendix
Analogue outputs:
Monitor output
Accuracy
Resolution
Factory settings
1...4 current / voltage
outputs
2 standard, 3...4 optional
Accuracy:
Resolution:
Factory setting:
Analogue input: 2
Control elements:
Interface:
0...2.55 V DC, burden > 10 kΩ, ≤ 100nF
2 % of measurement value, no better than 0.2 vol. % O
10 mV
0...2.55 V DC ≈ 0...25.5 vol. % O
Can be switched to probe voltage U-O2
0...2.55 V DC ≈ 0...255mV U-O2 using DIP-switches
Direct current
Burden
Direct voltage
Burden
Not floating (optional electrical isolation)
Measuring ranges and physical size can be configured
0.5 % output value, no better than 0.01mA
0.1 vol. % O
2
Output 1
0...10 vol. % O
Output 2
0...1000ppm
Optional
Via plug-in cards on the LT 2/KS1-DK power pack electronics
Analogue input card voltage -200...+1000mV
6 57 P 0660
Analogue input card potentiometer 1...5 kΩ
6 57 P 6000
Analogue input card current 0 / 4...20 mA
6 63 P 6001
Analogue input card 0 / 4...20 mA with 24 V DC supply for transducer
6 57 P 6002
Temperature input for PT 100 sensor
6 57 R 0890
Temperature range 0...320°C / 0...850°C
Resolution 1°C
Wall-mounted housing/mounting plate
Multi-function pushbutton, maintenance switch and 2 LED lines each
with 6 LEDs
Display and operating unit with graphic LCD
Remote display software (optional extra)
LAMTEC SYSTEM BUS
RS 232 only in conjunction with interface module 6 63 P 0500
87
2
0 / 4...20 mA (default)
0...600 Ω
0...10 V
≥ 10 kΩ
4...20 mA,
2
4...20mA
2