Magnetic Autocontrol MPH 112 Operating Instructions Manual page 69

High door pedestrian barrier
Hide thumbs Also See for MPH 112:
Table of Contents

Advertisement

CAN bus addressing and termination
58175005EN 01/2009 MPH-112
Version: 00
If a controller is replaced, e.g. during repairs, take care that the four
DIP switches correctly are reset on each of the three controllers.
In particular, wrongly set termination DIP switches can result in
faults during operation which are often hard to locate and occur only
intermittently.
If two controllers accidentally have the same address, or if one has
an inadmissible address, operation is not possible. In these cases
an error code is displayed at MBC-110.
4 DIP switches on each
for CAN addresses and termination
MBC-110
Fig. 11-3 Locations of DIP switches for CAN addresses and
MMC-120 Master
termination
MMC-120 Slave
Page 69/96