Appendix; General Notes; Diagnostics; Web Server Fault Codes - Siemens OZW672 Series Commissioning Instructions

Web server v4.0
Hide thumbs Also See for OZW672 Series:
Table of Contents

Advertisement

Text entry
Note
Fault codes
Siemens
Building Technologies
7

Appendix

7.1

General notes

Names of data points and message text, e.g. of faults, cannot contain special
characters or umlauts. Valid characters:
• a...z and A...Z
• 0...9
• ! „ $ % & ‚ ( ) * + ` - . / : ; < = > ? "Space
When sent, invalid characters will be converted to "?" (question marks).
7.2

Diagnostics

7.2.1

Web server fault codes

Fault code
Web server fault
General
0
No fault
Communications
81
No bus power supply
95
Invalid time of day (Web server time not or incorrectly entered).
100
>1 clock time master
142
Device failure (Bus)
171
[Fault input 1] fault
172
[Fault input 2] fault
438
Incorrect bus connected
439
Bus module not identified
448
Message receiver 1 not reached
449
Message receiver 2 not reached
450
Message receiver 3 not reached
451
Message receiver 4 not reached
System configuration errors
82
>1 identical device address (Devices have same address).
1) Device failure monitoring (Bus) is stopped if the bus has no power.
2) Created by the web server for the device failed.
Device failure (Bus) as a result, device failure (bus) is assigned to "System faults",
whereas all other faults generated by the web server are assigned as "Local faults".
3) Possible causes of recipient type e-mail: Erroneous Ethernet or e-mail settings.
Web server OZW672... V4.0
Appendix
1)
2)
3)
3)
3)
3)