CPU 210 Data Sheets
A.5

PDS 210 AC Power Supply, DC Inputs, Relay Outputs

Model Number: 6ES7 210-8XX00-6AA0
General Features
Physical Size (L x W x D)
197 x 80 x 62 mm
(7.76 x 3.15 x 2.44 in.)
Weight
0.5 kg (1.1 lbs.)
Power Dissipation
9 W maximum, with
maximum output loading
User Program Size / Storage
256 words (RAM)
I/O
4 Inputs / 4 Outputs
95 µs
Boolean Execution Speed
Internal Memory Bits
48 bits
Timers
4
Counters
4 (retentive)
Analog Adjustments
1
Standards Compliance
UL 508
FM Class I, Division 2
VDE 0160 compliant
CE compliant
Output Points
Output Type
Relay, dry contact
Voltage Range
5 to 30 VDC / 250 VAC
Maximum Load Current
per point
2 A
per common
4 A
Overcurrent Surge
7 A with contacts closed
Isolation Resistance
100 M minimum (new)
Switching Delay
10 ms maximum
Lifetime
10,000,000 Mechanical
100,000 with Rated Load
Contact Resistance
200 m maximum (new)
Isolation
coil to contact
1500 VAC, 1 minute
contact to contact
1000 VAC, 1 minute
Short Circuit Protection
None
A-10
Input Points
Input Type (IEC 1131-2)
ON State Range
ON State Nominal
OFF State Maximum
Response Time
I0.0 to I0.3
Interrupt I0.0
Optical Isolation
Power Supply
Voltage / Frequency Range
Input Current
CSA C22.2 142
Hold Up Time
Inrush Current
Fusing (non-replaceable)
Isolated
DC Sensor Supply
Voltage Range
Ripple/Noise (<10Mhz)
24 VDC Available Current
Short Circuit Current Limit
Isolated
Type 1 Sinking
15-30 VDC, 4 mA minimum
35 VDC, 500 ms surge
24 VDC, 7 mA
5 VDC, 1 mA
15 ms maximum
210 s on, 70 s off
1500 VAC, 1 minute
85 to 264 VAC at 47 to 63 Hz
4.5 VA typical, CPU only
50 VA max. load
20 ms min. from 110VAC
20 A peak at 264 VAC
2 A, 250 V, Slow Blow
Yes. Transformer, 1500 VAC,
1 minute
20.4 to 28.8 VDC
1 V peak-to-peak maximum
280 mA
< 600 mA
No